NBS Source
I'm a manufacturer
Compare variants

Worcester Greenstar HIU - Heat Interface Unit

Verified by manufacturer 6 months ago

HIU: 7-735-600-658

Bosch Thermotechnology Ltd Variant:

Twin plate heat exchanger, indirect heat interface units. BESA registered.

Jump to:
+44 (0)1905 754624 Website

Application

Provides domestic hot water and space heating for properties that use district heating or centralized boiler plants. Gives separation to the heat network system, helping to protect and provide improved control to individual properties on the network.

Highly efficient heat transfer for use on communal heat networks or larger district heating schemes. The HIU is BESA registered, allowing users to meet CIBSE CP1 (2020) guidance and best practice methods for the design of their networks.

Description

The Greenstar HIU is a range of twin plate heat exchanger indirect heat interface units, which offer DHW flowrates of up to 15 L/min or 21 L/min. All models offer up to 15 kW to central heating and the ability to accurately control priority DHW and central heating flow temperatures in increments of 5°C.


Features and benefits:

  • Greenstar HIU comes in three variants “HIU”, “HIU E” & “HIU KE”.
  • The “E” and “KE” models are both BESA registered
  • Model variants available with or without heat meter, DPCV and flushing bypass.
  • DHW output up to 73.3 kW (21 L/min) HIU KE and 52.3 kW (15 L/min) HIU, HIU E.
  • Central heating capacity of up to 15 kW.
  • Electronic control valves with return temperature limiter.
  • Fully insulated separate EPC inner case enclosing all major components.
  • Internal DPCV options.
  • All models offer both top and bottom connections.
  • Optional internal keyless filling loop.
  • Optional flushing bypass.
  • Easy internal pre-payment cut-off connection.
  • Internal anti scald valve protection.

General information

Color

White

Finish

Other

Material

Metal

Shape

Rectangle

Length

270 mm

Width

440 mm

Height

700 mm

Warranty description

Two year

Uniclass

Pr_60_60_38_36 Heat interface unitsPrimary

CAWS

T90/110 Heating system

T90/110 Heating system

Specification data - Heat interface units

Standard

Tested to BESA UK HIU Test regime.

Duty

-

Primary flow temperature

90℃.

Primary return temperature

22.3℃.

Pressure drop

0.8 bar.

Manufacturer guidance

Maximum differential pressure on primary side.

Flow rate

15 L/min.

Manufacturer guidance

Maximum DHW volumetric flow rate.

Heating supply temperature

70℃.

Hot water supply temperature

60℃.

Casing

Metal.

Insulation

-

Manufacturer guidance

Fully insulated separate EPC inner case enclosing all major components.

Components

-

Primary

Domestic hot water heat exchanger.

Guidance for specification option:

Heating exchanger, strainer and air vents.

Secondary

Pump.

Controls

Not required.

Electrical supply

230/50 V/Hz.

Ingress protection (IP) rating

X4D IP.

Power consumption

41.3 W (maximum); 3.1 W (standby).

Output

41.8 kW; 52.3 kW (maximum output).

Manufacturer guidance

DHW output (50°C DHW – 10ºC CWM).

DHW output (90°C primary, 60°C DHW) – Maximum output.

HeatOutput

1—15 kW.

Operating pressure (maximum)

10 bar.

Expansion Vessel Charge

5 L.

Expansion Vessel Size

0.75 bar.

Dimensions

700 x 440 x 270 mm.

Manufacturer guidance

Height x width x depth.

Inlet

22 mm.

Manufacturer guidance

Cold inlet.

Outlet

22 mm.

Manufacturer guidance

DHW outlet (compression).

Valve size

15 mm.

Manufacturer guidance

Pressure release valve.

Accessories

Not required.

Security fixings.

Guidance for specification option:

7-733-600-281.

Rear vertical piping kit.

Guidance for specification option:

7-733-600-127.

Flushing valve (compression).

Guidance for specification option:

7-733-600-133.

Flushing valve (flat face).

Guidance for specification option:

7-733-601-142.

Show more

Sustainability data

Contains Red List materials

No

Country of material origin

Europe

Country of product manufacture

United Kingdom

BIM objects

Platform Compatible Version
Revit
-

1