NBS Source
I'm a manufacturer

Wireless Fire Detection - Agile

Verified by manufacturer 22 hours ago

Morley-IAS

Addressable wireless fire detection system.

Jump to:
+44 (0) 203 4091779 Website

Application

Suitable for all applications where wired fire devices cannot be installed for economic or aesthetic reasons.

Description

The Morley Addressable Wireless Fire Detection System is a Hybrid (wired to fire detection loop via Gateway) next-generation platform of wireless fire devices designed for applications where wired devices are impractical due to economic or aesthetic constraints. Built on robust mesh network technology, the system ensures reliable communication by providing up to two communication paths for each device, significantly improving resilience compared to traditional star network architectures. Connects to the MAX and DXC control panels

As part of the Series 200 product range, the wireless system maintains the same high standards of device design, detection performance, false alarm immunity, and system functionality. Wireless devices can be seamlessly integrated into existing Morley-IAS panels supporting Series 200 protocols, allowing for straightforward system expansion and hybrid installations.

System configuration, commissioning, and diagnostics are managed via the Agile IQ™ software tool. Using a wireless USB dongle, the PC-based application communicates directly with wireless devices without the need for hardwired connections. Agile IQ™ supports Microsoft Windows operating systems from XP through Windows 10, providing a flexible platform for system management.

Features and benefits:

  • Wireless mesh network bidirectional communication technology.
  • Two communication paths to each wireless device.
  • 7RF channels at 865Mhz-867Mhz.
  • Two integrated antennas on each wireless fire device.
  • Up to 400 m free air communication range .
  • Up to five years average battery service life.
  • S200 Morley-IAS CLIP and Advanced Protocol loop communication.
  • Addresses set using S200 rotary switches.
  • Wired fire devices look and feel.
  • Patented battery service life prediction feature.
  • Loop powered Gateway.
  • Up to 8 Gateways per Morley MAX and MAX Plus Panel.
  • Up to 31 wireless detector/devices plus 17 wireless response indicators per Gateway.
  • Agile IQTM Easy wireless system design, configuration and diagnostics.
  • EN54-25 Certified.

General information

Color

White

Red

Finish

Smooth

Material

Plastic

Shape

Circle

Square

Uniclass

Ss_75_50_28_29 Fire detection and alarm systemsPrimary

CAWS

W90/125 Fire detection and alarm systems in non-domestic premises

W90/325 Fire detection and alarm control and indicating equipment

W90/120 Fire detection and alarm systems in domestic premises

Specification data - Fire detection and alarm systems

Classification data

System type

Addressable.

Detection devices

-

Atmosphere

Normal.

Types

22051TLE-RF - photo-thermal-IR detector.
22051E-RF - photo detector.
52051E-R - 58°C fixed temperature heat detector.
52051RE-RF - rate of rise heat detector.

Equipment interconnectivity

Radio-linked.

Cable containment

Wireless.

Internal alarms

-

Primary

Not required.
WSF-WR-RF - wall-mounted white/red sounder strobe.
WSO-RR-RF - wall mounted addressable sounder - red.
WSO-WW-RF - wall mounted addressable sounder - white.

Secondary

Not required.
M200I-RF - remote indicator.

Controls

M211E-RF - input/output module.

System accessories

Not required.
B501RF - detector base white.
B501RF-RR - detector base RED.
M200F-RF - repeater.
MI-GATE - gateway.

Ancillary components

Not required.
R5A-RF - waterproof manual call point.

Sustainability data

Material

Plastic