Third party accredited and is supplied and fitted with the manufacturer's Total Gravity Fail Safe (TGFS) system.

Jump to:
BIM object icon
+44 (0)23 9245 4405 Website

Application

Suitable to be used to form a virtually continuous barrier against smoke.

Description

An electrically operated active fire curtain barrier assembly. The barrier assemblies comprises a woven steel and glass fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.


The barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). The barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (60 minutes).


Operation:

Barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. During this period, the barrier assembly will deploy on receipt of a signal. At the end of the period, the barrier assembly will deploy.


Fire resistance:

180 minutes (3 hours) integrity.


Period of radiation:

115 minutes <15 kW/m².


Classification:

E180 EW30 C0.


Product certification, performance and/ or testing:

  • Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Complete barrier assemblies are certified with an independent accredited certification body operating an accredited United Kingdom Accreditation Service (UKAS) scheme for installation, commissioning and servicing.
  • Complete barrier assemblies have been tested for fire resistance to BS EN 1634-1 as required by BS 8524-1. The barrier assembly achieved 120 minutes integrity and 30 minutes radiation.
  • Complete barrier assemblies have been tested for smoke leakage to BS EN 1634-3 as required by BS 8524-1.
  • Complete barrier assemblies have been tested for impact to BS 5234-2 as required by BS 8524-1.
  • Complete barrier assemblies have been tested for reliability, durability and self-closing to BS EN 14600 as required by BS 8524-1.
  • Complete barrier assemblies have been tested for gravity fail-safe as required by BS 8524-1.
  • Complete barrier assemblies must show tested ability to adjust and control speeds on site to suit specific site requirements as required by BS 8524-1.
  • Motor(s) used within barrier assemblies in the above tests have been tested for operation at temperatures of 400°C as required by BS 8524-1.
  • The fabric used within the barrier assemblies have been tested to BS 476-6 and BS 476-7 and achieve a Class 0 rating.


Approving standards:

The following standards apply to this product:

  • BS 8524-1:2013, Specification for active fire curtain barrier assemblies.
  • BS EN 1634-1:2014, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows.
  • BS EN 1634-3:2004, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Smoke control test for door and shutter assemblies.
  • BS EN 1363-1:2012, Fire resistance tests – Part 1: General requirements.
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures.
  • BS EN 14600:2005, Doorsets and openable windows with fire resisting and/ or smoke control characteristics. Requirements and classification.
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests.
  • BS 476-6, Fire Propagation Tests.
  • BS 476-7, Surface Spread of Flame Tests.
  • BS EN ISO 9001:2008, Quality management system.
  • BS EN ISO 14001:2004, Environmental management system.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Steel

Fabric

Guidance for specification option:

Glass fabric.

Shape

Rectangle

Width

3000 mm

Height

3000 mm

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

BS 8524-1, BS EN 1634-1, BS EN 1634-3, BS EN 1363-1, BS EN 1363-2, BS EN 13501-2+A1, BS EN ISO 14184-1:2011, BS EN 14600:2005, BS 6323-5:1982, BS EN ISO 9001, BS EN ISO 14001, ISO Guide 65, BS EN 45011, BS 5234-2, BS EN 14600.

Size

Guidance for specification option:

Insert requirement, width up to 30 m, height up to 6 m.

Performance

-

Durability class

C0.

Fire resistance

180 minutes (3 hours) integrity.

Barrier units

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ 2/1000/DGI, which is a stainless steel wire reinforced glass fabric coated with an intumescent graphite silocone elastomer. It has an area weight of 1900 g/m² –5% +10%.
  • The fabric has passed testing to BS 8524-1, BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance).
  • The fabric has passed testing to BS 476 part 6 (Fire Propagation Tests) and part 7 (Surface Spread of Flame Tests).

Deployment

Full.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Beam protection and obstruction warning.

Guidance for specification option:

Will sound in the event of an obstruction being placed at the barrier drop line.

Emergency retract.

Guidance for specification option:

Touch-button retract facility for multi-escape.

Split drop delay.

Guidance for specification option:

Will partially deploy to pre-determined level to permit escape.

Visual alert system.

Guidance for specification option:

Light warning system.

Voice warning.

Guidance for specification option:

Auto-spoken multi-message facility.

Classification

E180 EW30 C0.

Frame colour/ finish

Guidance for specification option:

Insert requirement.

Opening sizes

Guidance for specification option:

Insert requirement, width up to 30 m, height up to 6 m.

Finish

Galvanized

Zintec

Painted

Manufacturer guidance

Insert requirement.

Accessories

None.

Beam protection and obstruction warning.

Guidance for specification option:

Will sound in the event of an obstruction being placed at the barrier drop line.

Emergency retract.

Guidance for specification option:

Touch-button retract facility for multi-escape.

Split drop delay.

Guidance for specification option:

Will partially deploy to pre-determined level to permit escape.

Visual alert system.

Guidance for specification option:

Light warning system.

Show more

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BIM object icon

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit

Revit 2017

1

IFC
-

1

Similar products from Coopers Fire Ltd

FireMaster® 4/1000 - Vertical Active Fire Curtain

FireMaster® 4/1000 - Vertical Active Fire Curtain

FireMaster® A1 - Active Fire Curtain

FireMaster® A1 - Active Fire Curtain

FireMaster® A1 ResQ-Window

FireMaster® A1 ResQ-Window

FireMaster® Cleanroom - Vertical Active Fire Curtain

FireMaster® Cleanroom - Vertical Active Fire Curtain

FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain

FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain

FireMaster® Concertina Open - L Shape - Concertina Fire Curtain

FireMaster® Concertina Open - L Shape - Concertina Fire Curtain

FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain

FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain

FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain

FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain

FireMaster® Concertina™ Egress Fire Curtain

FireMaster® Concertina™ Egress Fire Curtain

FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain

FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain