Verified by manufacturer 29 days ago
30-Stage Electric Boilers: EP 1200
ISO 9001 Quality Management
Certificate type
Three phase electric boilers.
Suitable for heat networks, schools, care homes, other commercial buildings and industrial applications.
Three phase electric boilers for heat networks, schools, care homes, other commercial buildings and industrial applications. The range consists of boilers from 31 kW to 1400 kW outputs and their operating range is between 20°C to 95°C.
Modulating power output is particularly important in hybrid systems where electric boilers need to operate in harmony with other heat sources such as CHPs and heat pumps. Varmebaronen boilers modulate their power output in 7, 15 or 30 steps. The output of the boilers can be limited to only one power step.
Features and benefits:
Color | Grey |
Finish | Painted |
Material | Steel |
Shape | Rectangle |
Length | 540 mm 670 mm 882 mm 1063 mm 1327 mm |
Width | 455 mm 504 mm 662 mm 1059 mm 1638 mm |
Height | 1105 mm 1390 mm 1651 mm 1655 mm 2037 mm |
Warranty description | Two year |
Uniclass | |
CAWS | T90/322 Boilers, electric |
Boiler type | Electric. |
Output | 1200 kW.Manufacturer guidanceMaximum power. |
Energy efficiency rating | Class D. |
Mounting | Floor-mounted. |
Operating pressure | 6 bar (600 kPa). |
Test pressure | 8.6 bar. |
Operating temperature | 20–95℃. |
Flow rate (minimum) | 11.5 L/s. |
Heat exchanger | Not required.Pressure break.Guidance for specification option: Optional. |
Electrical supply type | Three-phase. |
Casing material | Manufacturer's standard. |
Accessories | Not required.Safety equipment.Series controller.Internal cooling fan.UTK, outdoor temperature compensator.Secondary temperature controller. |
Current | 1732 A. Manufacturer guidanceCurrent at maximum power. |
Power | 40 kW. Manufacturer guidancePower stage. |
Flange | 4 x FL 33, 2x ⌀60 mm. Manufacturer guidanceCable flange. |
Connection | 8 x 95–240 Cu/AI. Manufacturer guidanceCable connection mm². |
Pipe connector | Flow/ return: DN 150/ PN 16. |
Weight | 930 kg. Manufacturer guidanceWeight, not filled with water (kg). |
Clearance | 2500 mm. Manufacturer guidanceMinimum clearance. Floor to ceiling. |
Dimensions | 2037 x 1638 x 1327 mm. Manufacturer guidanceH x W x D. |
Ingress protection | IPX1. Manufacturer guidanceEnclosure protection class. |
Country of product manufacture | Sweden |
Material | Steel |
Manufacturing plant location | |
Expected Life | 20 year |
Platform | Compatible | Version |
---|---|---|
- | 1 |