IFCC
Certificate type
A WALKTHRU™ smoke barrier with the Total Gravity Fail Safe (TGFS) system.
Suitable for use in atria, lobbies and receptions, opening in walls, egress and corridor separations, boundary protection, compartmentation, stairs and escalators, lifts and lift lobbies and protected means of escape.
A patented bi-roller system which has interweaving, overlapped panels as narrow as 600 mm wide. Each panel overlaps the other and has its own self levelling bottom ballast system. Evacuees can simply ‘WALKTHRU™’ the panels which then fall back into place, helped by the patented anti-tangle overlap retention system.
Complies with the Equality Act. It is an active smoke barrier comprising technologically advanced fire-resistant fabric barriers encased in a compact steel housing. Barriers remain invisibly retracted until activated by an alarm or detector signal, at which time they descend safely to their fire operational position.
To be compliant, smoke barriers must be protected from a short circuit and or total power failure, this is achieved with the patented Total Gravity Fail Safe (TGFS) system. Smoke barriers will control the spread of smoke in a building and protect the means of escape and create tenable conditions.
Operation:
When activated, the smoke barrier descends at safe controlled speeds in accordance with the Machinery Directive. Evacuees can then approach the barrier quickly, safely and see if anyone is coming the other way.
Approved escape signs can show which panels to pass through to avoid collision and tangling. When retracting, the combination of sequential ascent, the re-aligning panel system with the divide and separating bi-roller system ensures a trouble free operation.
Bottom edge:
The flexible bottom edge of each barrier panel nominally weighs between 2–4 kg depending on overall unit width. The bottom ballast weights should be kept as low as possible to finished floor level to enable easy egress. The bottom ballast weights are sufficient enough to return the panels to their operational position within 5 seconds of an evacuee passing through.
Box:
Encloses the curtain and barrel assembly, manufactured from 1.5 mm galvanized steel.
Barrel assembly:
Patented steel bi-rollers.
Motor drive unit:
Inboard 24 V d.c. motor including necessary drive mechanisms, a mechanical epicyclic gearbox retarder, automatic overload protection and both automatic and manual distance travel positioning, switches all linked to an internal 24 V d.c. electromagnetic brake with regenerative braking system.
Fail-safe release device:
Split deployment:
As the barrier assemblies may cross potential escape routes, a split deployment function is available to encourage safe evacuation psychology. Upon receipt of a fire alarm or through loss of power, the barrier assemblies drop to a set height above the finish floor level for a predetermined period of time. After this time has been completed, half of the curtain panels will deploy to their deployed position whilst the other half remain retracted for a second predetermined period of time. After this time the remaining barrier panels deploy to their final fire operational position. This process assists in a calmer evacuation procedure.
Fire resistance:
150 minutes (2½ hours) integrity at 600°C (1112°F).
Power supply:
230 V a.c. 50 Hz dedicated supply via 13 A un-switched fused spur. Backup battery: Two 12 V, 7 A/h lead acid batteries.
Alarm signal:
Normally closed volt-free contacts, open on activation.
Display:
Power on, alarm active and alarm off.
Standards:
CE marked to BS EN 12101-1:2005+A1:2006 as required by the Construction Products Regulations (CPR).
Color | Other |
Finish | Galvanized Zinc plated Powder-coated |
Material | Fabric Guidance for specification option:
|
Shape | Rectangle |
Length | Bespoke Manufacturer guidancePower supply size |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | BS EN 12101-1+A1, BS EN 1363-1, BS EN 1634-3, BS EN 13501-4, BS EN ISO 1716, BS EN 13501-1, BS 476-6+A1, BS 476-7. |
Barrier assemblies | To BS EN 12101. |
Test standards | To BS EN 12101-1+A1, BS EN 1363-1, BS EN 1634-3, BS EN 13501-4, BS EN ISO 1716, BS EN 13501-1, BS 476-6+A1, BS 476-7. |
Third-party certification | IFC. |
Size | 400 x 500 x 210 mm.Guidance for specification option: Power supply size (w x h x d). Manufacturer guidanceInsert requirement, available in unlimited widths (600 mm minimum) and drops up to 6.7 m. |
Performance | |
Pressure and impact | SD. |
Durability class | C1. |
Smoke containment | To BS EN 12101. |
Fire resistance | 150 minutes (2½ hours) integrity at 600°C (1112°F). |
Reaction to fire | To BS EN 13501-4, up 150 minutes. |
Barrier units | Single.Multiple. |
Deployment | Full. |
Accessories | None.Beam protection and obstruction warning.Mechanical override.Signage.Split drop delay.Guidance for specification option: Partially deploys to pre-determined level to permit escape and initial smoke containment. Translucent fabric.Visual alert system.Guidance for specification option: Light warning system when mains or emergency power is available. Voice warning.Guidance for specification option: Audio or spoken multi message facility when mains or emergency power is available. |
Classification | D600A, A1. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Recyclability | Coopers Fire offer a take back service where product is broken down into component parts. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |