Siderise RV vertical cavity barriers for rainscreen cladding are used to full fill the void between the external envelope and internal structure, providing an effective hot smoke and fire seal.
Siderise RV vertical cavity barriers for rainscreen cladding are used to full fill the void between the external envelope and internal structure.
The construction offers excellent resistance to the passage of both smoke and fire. Additionally, by fully sealing the void, they assist ventilated façades to function by maintaining air-pressurisation compartmentation.
Significantly, their unique stonewool lamella core construction enables the vertical barriers to accommodate the serviceability movement normally associated with rainscreen façades.
Intersections between horizontal and vertical cavity barriers are simply abutted, with RFT 120/45 foil tape applied as detailed in the RV Installation Instructions. The leading edge compresses directly against the external envelope. No intumescent strip is required.
Siderise RV vertical cavity barriers for rainscreen cladding applications consist of a non-combustible stonewool lamella core, with reinforced aluminium foil faces.
Siderise RV vertical cavity barriers are installed within the cavity formed between the rainscreen facade and the inner structural wall using appropriate Siderise support brackets. Brackets are available in either galvanised mild steel (G) or stainless steel (S).
The standard product length is 1200mm
Resistance to Fire - Siderise RV vertical cavity barriers have been tested in accordance with EN 1366-4: 2006+A1: 2010. The cavity barriers maintained integrity (E) and insulation (I) requirements. This is detailed in the manufacturers technical data sheet.
The tests have been undertaken to assess the ability of the vertical-cavity barrier products to reinstate the fire resistance of a lightweight aerated concrete supporting construction. This is the standard assembly for testing such cavity barrier products as it allows the performance of the individual barrier to be classified.
Features and benefits:
Color | Silver Brown Manufacturer guidanceGrey with silver shades aluminium top and bottom faces with. Solid, green-brown on exposed mineral wool side faces. |
Finish | Foil Guidance for specification option: Foil. |
Material | Stonewool |
Shape | Rectangle |
Length | 1200 mm |
Width | Bespoke Manufacturer guidanceWidth = Void size + 10mm compression (Minimum) Width range = 30 - 460mm (Minimum) |
Height | Manufacturer guidancePlease see product Thickness. |
Uniclass | |
CAWS | H92/776 Thermal insulation P12/360 Mineral wool rigid batts P12/40 Mineral wool rigid batts |
Product range |
Third-party certification | CF 6028 and IFCC 1712. |
Cavity barriers | |
Sleeves | Aluminium foil facing to top and bottom. |
Size | Manufacturer guidanceSupplied pre-cut in widths to suit advised void size. |
Residual cavity width | Void widths of 20–450 mm. |
Length | 1200 mm. |
ThermalConductivity | 0.038 W/m·K. |
Fixing brackets | Not applicable. Guidance for specification option: For void widths 20–50 mm. B65/110. Guidance for specification option: For void widths 51–150 mm. B195. Guidance for specification option: For void widths 151–240 mm. B355. Guidance for specification option: For void widths 241–300 mm and 301–450 mm.. Manufacturer guidanceSupport brackets should be installed at 600 mm fixing centres (300 mm from each end). Brackets supplied as standard in 1 mm galvanized mild steel (G) or stainless steel (S), in a flat form for site folding. They incorporate pre-notched indents to aid this process. Consult manufacturer's literature for more information. |
Fire resistance (integrity and insulation) | Integrity (E): 90 minutes; Insulation (I): 30 minutes. |
Void width | 20–50 mm. Guidance for specification option: Measured cavity +5 mm/ +10% compression is required. 51–450 mm. Guidance for specification option: Measured cavity +10 mm compression is required. Manufacturer guidanceFor voids greater than 450 mm, contact manufacturer's technical services team for further information. |
Thickness | 75 mm. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Material | Stonewool |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 1.72 kg CO₂ eq/kg Guidance for specification option: 1.72+E00 kgCO2e/kg |
Recyclability | Recyclable Manufacturer guidanceThe stone wool core is recyclable |
Expected Life | 60 year Guidance for specification option: When correctly installed in open cavities in façade applications, the Siderise ‘RV’ and ‘RH’ Cavity Barriers for Rainscreen Cladding have an expected service lifespan of 60 years. |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 2 | |
- | 2 |