SIDERISE RF cavity fire barriers and firestops are used in raised access floors to prevent the spread of fire and smoke, and reduce sound transmission, providing up to 120mins fire resistance.

Jump to:
+44 (0)1656 730833 www.siderise.com
Description

SIDERISE RF raised access floor system has been specifically developed to provide cavity fire stops for use in voids between raised access floors and floor slabs. It is designed as a one-piece system and allows easy cutting and installation. The product also offers unique vertical compression to allow tightness of fit.

SIDERISE RF-CB cavity barrier systems:

Used to subdivide uninterrupted voids in accordance with Building Regulations offering 30 minutes fire resistance, (EI 30). CB barriers are designed to suit individual floor void depths of 50–600 mm.

SIDERISE RF-FS fire stop systems:

Maintains continuity of fire resistance for installations aligned with fire rated partitions, hence maintaining compartmentation. The FS system offers 60–120 minutes fire resistance. FS barriers are designed to suit individual floor void depths of 50–600 mm.

Features and benefits:

  • Economical and easy to install.
  • Offers excellent acoustic performance.
  • Provides a smoke and fire seal.
  • Provides excellent lateral compression.
  • Provides up to 120 minutes fire integrity and insulation.
  • Quality assured to BS EN ISO 9001.
  • Suitable for use in air plenum applications.
  • Suitable for use in voids heights up to 1000 mm.
  • Supplied in sheet form, for cutting on site, or pre-cut in strips to suit specific void height.
  • Tested utilizing the principles of BS 476-20 and BS EN 366-4.

General information
Finish

Bright aluminium foil

Color

Silver

Features

Quick and simple to install, High fire and acoustic performance

Size

1200 x 1200mm

1200 x 1175mm

Uniclass 2015
Pr_25_80_81_51 Mineral wool fire-stoppingPrimary
CAWS

K41/340 Cavity barriers

P12/360 Mineral wool rigid batts

P12/40 Mineral wool rigid batts

Specification data - Mineral wool fire-stopping
Product Reference

RF-CB 30

30 minutes' fire rating, 75 mm thick. 21 dB (Rw).

RF-FS 60

60 minutes' fire rating, 90 mm thick. 23 dB (Rw).

RF-FS 120

120 minutes' fire rating, 120 mm thick. 25 dB (Rw).

RF-CB 30 X

30 minutes' fire rating, 90 mm thick. 23 dB (Rw).

RF-FS 60 X

60 minutes' fire rating, 120 mm thick. 25 dB (Rw).

Fixing brackets

Insert requirement, contact manufacturer's literature for more information.

Standard product features

Material:

Non-combustible, rock mineral wool lamella core faced with Class O reinforced aluminium foil on both sides.

Length:

  • Square edged: 1200 mm.
  • Rebated edge: 1175 mm.

Width:

Available in sheet form of 1200 mm or pre-cut to suit the void height; contact manufacturer for more information.

Sound reduction:

21–25 dB (Rw).