Verified by manufacturer 4 months ago
QA Certificate
Certificate type
EPD
Certificate type
PSA light grade access floor system.
Light office use.
Light grade access floor system - uniformly distributed load (UDL): 6.7 kN/m². The fully encapsulated panel comprises of a wraparound steel top and a steel base plate that are adhesively bonded and mechanically stitched around a particleboard core for greater strength and durability.
Features and benefits:
Warranty only valid when a full Kingspan Access Floor system including panels and understructure is installed.
Color | Silver |
Finish | Galvanized |
Material | Particleboard Core material: 30 mm high density particleboard. Steel |
Shape | Square |
Length | 600 mm |
Width | 600 mm |
Height | 31 mm |
WarrantyDescription | 25 year Full 25-year system warranty. Warranty is only valid when a full Kingspan Access Floor system including panels and understructure is installed. |
Uniclass | |
CAWS | K41/130 Raised access floor |
System performance | Light grade to MOB PF2 PS/SPU. |
Subfloor preparation | Dustproofing sealers. |
Support structure typeSteel pedestals are coated with an environmentally friendly clear passivation as standard. | Access floor pedestals - Alpha III, steel.For voids ≥ 610 mm. Steel as standard. Access floor pedestals - Alpha V, steel.For voids 25–610 mm. Steel as standard. Access floor pedestals - Alpha III, nickel plated.For voids ≥ 610 mm. Nickel-plated - optional. Access floor pedestals - Alpha V, nickel plated.For voids 25–610 mm. Nickel-plated - optional. |
Pedestal fixings | Polyurethane (PUR) adhesives (standard).Polyurethane (PUR) adhesives (acoustic). |
Raised access floor surface | Raised access floor panels. |
Barriers in floor void | - |
Plenum barriersThe system can be supplied with neoprene gaskets to minimize air loss through the raised floor surface from the underfloor plenum to aid air circulation, distribution and management. | Not required.Required. |
System accessories | None.Pivot-head adaptors. |
Additional requirements | None. Simploc screw down. Pre-drilled holes for fixing, whilst allowing full access to the void. |
Category | Loose lay. |
Panel sizeThickness: 31 mm. | 600 x 600 mm. Standard. 600 x 900 mm (medium grade). Optional for perimeter detailing. 600 x 900 mm (heavy grade). Optional for perimeter detailing. |
Stringers | Not required. Clip-on stringer. For lateral stability in 600–800 mm void heights. Screw-down stringer. For lateral stability in > 800 mm void heights. |
Weight | System weight: 31 kg/m². |
Contains Red List materials | No |
Country of product manufacture | United Kingdom |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 6.2 kg·CO₂e/kg |
Recyclability | 99% recyclable |
Recycled content | 70 % |