Verified by manufacturer 6 months ago
EPD
Certificate type
PSA light grade access floor system.
Light office use.
Light grade access floor system - uniformly distributed load (UDL): 6.7 kN/m². The fully encapsulated panel comprises of a wraparound steel top and a steel base plate that are adhesively bonded and mechanically stitched around a particleboard core for greater strength and durability.
Features and benefits:
Warranty only valid when a full Tate Access Floor system including panels and understructure is installed.
Please contact us for the EPD or more information on the environmental performance of the product
Color | Silver |
Finish | Galvanized |
Material | Particleboard Guidance for specification option: Core material: 30 mm high density particleboard. Steel |
Shape | Square |
Length | 600 mm |
Width | 600 mm |
Height | 31 mm |
Warranty description | 25 year Guidance for specification option: Full 25-year system warranty. Warranty is only valid when a full Kingspan Access Floor system including panels and understructure is installed. |
Uniclass | |
CAWS | K41/130 Raised access floor |
System performance | Light grade to MOB PF2 PS/SPU. |
Subfloor preparation | Dustproofing sealers. |
Support structure type | Access floor pedestals - Alpha III, steel. Guidance for specification option: For voids ≥ 610 mm. Steel as standard. Access floor pedestals - Alpha V, steel. Guidance for specification option: For voids 25–610 mm. Steel as standard. Access floor pedestals - Alpha III, nickel plated. Guidance for specification option: For voids ≥ 610 mm. Nickel-plated - optional. Access floor pedestals - Alpha V, nickel plated. Guidance for specification option: For voids 25–610 mm. Nickel-plated - optional. Manufacturer guidanceSteel pedestals are coated with an environmentally friendly clear passivation as standard. |
Pedestal fixings | Polyurethane (PUR) adhesives (standard). Polyurethane (PUR) adhesives (acoustic). |
Raised access floor surface | Raised access floor panels. |
Barriers in floor void | |
Plenum barriers | Not required. Required. Manufacturer guidanceThe system can be supplied with neoprene gaskets to minimize air loss through the raised floor surface from the underfloor plenum to aid air circulation, distribution and management. |
System accessories | None. Pivot-head adaptors. |
Additional requirements | None. Simploc screw down. Guidance for specification option: Pre-drilled holes for fixing, whilst allowing full access to the void. |
Category | Loose lay. |
Panel size | 600 x 600 mm. Guidance for specification option: Standard. 600 x 900 mm (medium grade). Guidance for specification option: Optional for perimeter detailing. 600 x 900 mm (heavy grade). Guidance for specification option: Optional for perimeter detailing. Manufacturer guidanceThickness: 31 mm. |
Stringers | Not required. Clip-on stringer. Guidance for specification option: For lateral stability in 600–800 mm void heights. Screw-down stringer. Guidance for specification option: For lateral stability in > 800 mm void heights. |
Weight | System weight: 31 kg/m². |
Contains Red List materials | No |
Country of product manufacture | United Kingdom |
Material | Particleboard Guidance for specification option: Core material: 30 mm high density particleboard. Steel |
Recyclability | 99% recyclable |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 70 % |
Certified