A ½” exposed single sequential thermostatic mixing valve supplied complete with integral strainers.
A ½" exposed, single sequential thermostatic mixing valve, TMV2 and TMV3 approved for use in both the health care and residential sectors. Units provide high flow rates at low pressures and safe thermostatic shut down in less than 2 seconds.
Features and benefits:
Color | Silver |
Finish | Chrome |
Material | Brass |
WarrantyDescriptionTwo years parts and labour as standard; extended to five years parts and labour if commissioned by Rada. UK only. | - |
Uniclass | |
CAWS | S90/680 Thermostatic mixing valves S90/680 Thermostatic mixing valves |
Product range |
Approvals | Water Regulations Advisory Scheme (WRAS) approved. |
Standards | To BS 7942, BS EN 1111 and BS EN 1287. |
Form | Thermostatic mixing valve. |
Materials | - |
Body | DZR brass. |
Finish and colour | Chrome plated. |
Water supply temperature (maximum) | 85°C.
For safety reasons it is recommended that hot water storage temperature is maintained at between 60-65°C in ablutionary applications. The performance specification outlined below is achieved with the outlet blend temperature set between 35°C and 45°C, with supply temperature of 15°C cold and 65°C hot and nominally equal inlet supply pressure. Outlet blend water temperature is maintained within 2°C with a 10°C change in hot or cold supply. Shutdown of outlet flow to seepage within two seconds in the event of failure in either the hot or cold water supply, providing the blend temperature differs from the inlet supply temperature by at least 10°C. The valve will maintain control with a pressure loss ratio of up to 10:1. |
InletConnectionSize | 15 mm compression. |
Outlet connector | Reversible, ½" BSP male or 15 mm compression. Reversible outlet connector. |
NominalPressureDropPressure loss ratio. | 10:1. Maximum. |
Pressure | 0.1 bar.
|
NominalStaticPressure | 10 bar. Maximum. |
Operation | Sequential control, for use in both the health care and residential sectors. All V8/3 valves (excluding lockshield model) are operated via a single sequential control, which, when rotated, initially opens the valve, then increases the temperature from cold to a pre-settable maximum temperature stop. |
Country of product manufacture | United Kingdom |
Platform | Compatible | Version | Certified to |
---|---|---|---|
![]() | Revit 2016 | 4 | 1.3 |
![]() | - | 6 | 1.3 |
![]() | - | 1.0 | 1.0 |