1/2" point-of-use thermostatic mixing valve suitable for 'under-basin' installation.

Jump to:
+44 (0)844 571 1777 www.radacontrols.com
Description

A ½" point of use, thermostatic mixing valve, supplied with integral check valves and strainers.

General information

Color

White

Features

Suitable for ‘under-basin’ or duct installation; Safe thermostatic shutdown in less than 2 seconds; Supplied in white easy clean casing; Complete with integral check valves and strainers; Tamper proof temperature adjustment

Material

Body: DZR brass and housed in a white plastic casing

Size

15

WarrantyDescription

Two years parts and labour as standard; Extended to five years parts and labour if commissioned by Rada. UK only

Uniclass 2015

Pr_65_54_95_48 Low-temperature thermostatic mixing valvesPrimary

CAWS

S90/67 Thermostatic mixing valves

S90/680 Thermostatic mixing valves

Specification data - Low-temperature thermostatic mixing valves

Product Reference

Meynell 15/3 Thermostatic Mixing Valve (PESM0620J)

Standard product features

A ½" thermostatic mixing valve with integral check valves and strainers, suitable for under-basin installation and providing thermostatic shutdown in less than 2 seconds.

The unit also incorporates tamper proof temperature adjustment.

Operation:

Designed to be installed into the supply pipework and must be used with a separate outlet flow control such as a tap.

Connections:

Inlet and outlet: 15 mm compression fittings.

Pressure:

  • Minimum operating pressure: 0.1 bar.
  • Maximum static pressure: 10 bar.
  • Maximum pressure loss ratio: 10:1 (in favour of either supply).
  • Maximum hot water supply temperature: 85°C.
  • Maximum cold water supply temperature: 25°C.

Note: Both hot and cold pressures should be nominally equal.

Temperature range:

  • Factory pre-set maximum outlet temperature: 42°C.
  • Minimum temperature differential between hot inlet and pre-set outlet temperature: 10°C.
  • Optimum temperature control range: 35–45°C.
  • Maximum hot water temperature: 85°C (for safety reasons it is recommended that the hot water storage temperature is maintained at between 60°C and 65°C in ablutionary applications).

Materials:

Body: DZR brass housed in white plastic casing.

Digital objects
PlatformCompatibleVersionCertified to
IFC
- 1 1.3
Revit
Revit 2016 1 1.3
Download now from NBS National BIM Library
Third party certifications
  • BS 7942 : For high and low pressure use on washbasins and showers
  • BS EN 1111
  • BS EN 1287
  • Buildcert: Certificate - ETC/200/1202 : Buildcert TMV3 Thermostatic Mixing Valve Scheme approved
  • Water Regulations Advisory Scheme (WRAS) approved