NBS Source
I'm a manufacturer
Compare variants

QuelCast Cast-In Fire Collar

Verified by manufacturer 6 months ago

QUELCAST50

Quelfire Variant:
Third party certifications:
  • CE Marking

    Certificate type

QuelCast Cast In Fire Collar prevents the spread of fire through plastic pipe and cable penetrations in concrete floors.

Jump to:
+44 (0) 161 928 7308 Website

Application

QuelCast Cast In Fire Collar prevents the spread of fire through plastic pipe and cable penetrations in concrete floors.

Description

QuelCast Fire Collars are constructed from a robust polypropylene material and contain a high performance intumescent material which reacts under the influence of heat. This will exert pressure on the pipe as it softens, to form a carbonaceous char which provides an effective insulation plug thus preventing smoke and fire passing through to the adjoining compartment.


Features and benefits:

  • Suitable for a range of plastic combustible pipes including polyvinyl chloride (PVC), unplasticized polyvinyl chloride (PVC-U), polyethylene (PE), high-density polyethylene (HDPE), medium-density polyethylene (MDPE) and polypropylene (PP)
  • Available to suit 50, 110 and 160 mm and other diameter plastic pipes
  • Available to suit 150mm or thicker concrete slabs
  • Manifold recess former option (110 mm diameter pipes only)
  • Quick and simple installation
  • Integrated smoke seal
  • Strong lid to carry foot traffic and light access equipment
  • No backfilling generally required
  • Compact footprint allows for closer positioning of pipes
  • Manufactured in the UK


Standards and approvals:

  • Fire resistance testing to BS EN 1366-3
  • Up to EI 240
  • CE Marked
  • Performance unaffected by weathering (Type X Durability)
  • Classified to EN 13501-2


Installation:

The standard QuelCast is 250mm high to suit a 250mm deep concrete slab but they can be reduced or extended to suit differing slab depths – this is a service that Quelfire offer in house so that the product is delivered to site ready to install, however it can be done on site too.


For instances where the slab depth is between 250 and 150mm, the process is: Remove the cap, Cut the top off with a saw, replace the cap and finally, we recommend sealing the cap with self-adhesive tape to ensure no concrete seepage.


For instances where the slab depth is greater than 250mm the QuelCast is fitted with an extension tube. To install these the process is: Remove the cap, insert the tube over the QuelCast body pushing down until fully seated, measure up from the base, cut the extension tube with a sharp saw or knife, replace the cap and finally, we recommend sealing the cap with self-adhesive tape to ensure no seepage.


Simple installations steps:

  1. Mark the formwork with a cross where the pipe is to pass through the floor
  2. Position the QuelCast CE Marked Cast In Fire Collar as required (the centre line marks on the QuelCast Collars and Manifold help to position in the correct location)
  3. Attach to the formwork using screws or nails through the holes in the 4 corners of the unit
  4. Pour the concrete to the required depth
  5. On completion of concrete curing, remove all formwork and shuttering
  6. Remove the cap from the top of the QuelCast Collar
  7. Place the pipe through the QuelCast Collar


Additional instructions for QuelCast50:

No extra work, backfill or sealant is required where the correct diameter pipe is used in the correct QuelCast. For QuelCast50, cable bunches and where smaller diameter pipes are used inside larger collars a mineral wool smoke seal backfill is required in the top of the QuelCast.


For 110mm diameter pipes inside a QuelCast110 and 160mm in a QuelCast160, no backfill is required.


For more in depth installation information refer to the associated "Installation Installation" document.


QuelCast Manifold Recess Former

The QuelCast Manifold has been designed and developed to create a 70 mm recess in the floor slab either on the top or on the bottom of the floor slab to allow for applications where there is limited ceiling space and so the plastic pipe can be installed closer to the ceiling with the pipe connection recessed in the slab.


For example:

  • Soil pipe manifolds
  • Pipe connections
  • Limited ceiling space


When installing a QuelCast Manifold Recess Former to the underside of the slab the process is: cut the spigot off the manifold, position the QuelCast on the manifold within the indentations, secure together using self tapping screws through each corner of the QuelCast body and then install as a whole unit using the centre line indicators on the Manifold Recess Former as a guide instead of the QuelCast.


When installing a QuelCast Manifold Recess Former on the top of the slab, the process is: remove the cap, cut/extend the QuelCast body to suit the slab depth taking into consideration the depth of the Manifold Recess Former, push the Manifold onto the QuelCast until fully seated, ensure the temporary shuttering infill is in place and sealed with tape and then install the whole unit as normal.

General information

Color

Black

Guidance for specification option:

Grey-black.

Orange

Material

Intumescent

Polypropylene

Shape

Circle

Guidance for specification option:

Cylindrical.

Width

50 mm

110 mm

160 mm

Uniclass

Pr_65_52_61_15 Concealed intumescent pipe collarsPrimary

CAWS

P12/43 Pipe collar

P12/370 Pipe collar

Specification data - Concealed intumescent pipe collars

Sizes

250 mm.

Guidance for specification option:

Standard height.

Fire performance

Reaction to fire: Class F, Fire rating: ≤4 h (EI 240).

Guidance for specification option:

  • Class F to EN 13501-1.
  • Fire rating when used in conjunction with QuelCast 110.
  • Fire resistance testing to BS EN 1366-3: 2009.

Manifold recess former

Not required.

QuelCast manifold.

Guidance for specification option:

  • For QUELCAST110 only (110 mm diameter pipes only).
  • Creates a 75 mm recess in the floor slab either on the top or bottom, to allow for applications where there is limited ceiling space and the plastic pipe can be installed closer to the ceiling, with the pipe connection recessed in the slab.
  • Applications include: Shower traps for walk-in showers and wet rooms, soil pipe manifolds, pipe connections and areas with limited ceiling space.

Slab depth

150–250 mm.

Guidance for specification option:

Pre-cutting service is available; consult manufacturer for details and insert requirements.

250 mm.

Guidance for specification option:

Standard.

>250 mm.

Guidance for specification option:

Extension tube is available; consult manufacturer for details and insert requirements.

Diameter

For 50 mm diameter pipes.

Solubility in water

Insoluble in water and generally chemical inert.

Upper temperature stability

Expands greatly if heated above 200°C.

Form

Grey-black solid laminate encased in circular polypropylene shell.

Position

Cast-in device.

Sustainability data

Country of product manufacture

United Kingdom

Material

Intumescent

Polypropylene

Third party certifications

CE Marking

Certificate of Constancy of Performance - QuelCast Cast In Fire Collar

Literature

Product Data Sheet - QuelCast Cast In Fire Collar

Product Data Sheet - QuelCast Cast In Fire Collar

Installation Instructions - QuelCast Cast In Fire Collar

Installation Instructions - QuelCast Cast In Fire Collar

Similar products from Quelfire

CFC Ceiling Fan Cuff

CFC Ceiling Fan Cuff

QWR Intumescent Fire Collar for Plastic Pipes

QWR Intumescent Fire Collar for Plastic Pipes