NBS Source
List your products

This product is no longer available

PHLR Pro
Application

Detection of hydrocarbon liquids in interstitial spaces of tanks, pipes, sumps or other containment areas where hydrocarbon liquid can accumulate to a depth of 1/4" or more.

Consult manufacturer's literature for examples of:

  • Contained pipe;
  • Pressurized containment;
  • Sump;
  • Contained area.

Description

Resettable hydrocarbon probe.


Features and benefits:


  • Detects hydrocarbon liquids in interstitial spaces of tanks and pipes, sumps and other containment areas where hydrocarbon liquid can accumulate to a depth of ¼” or more.
  • Detectable liquids include: gasoline, diesel fuel, jet fuel and crude oil.
  • Ignores vapours.
  • Compact, durable design.
  • Fast respond time.
  • Relay-output capable.
  • Sensor elements swell upon exposure to hydrocarbon liquids to activate a sealed switch. Sensor elements can be cleaned and reused multiple times, allowing a quick reset time.
  • A PHLR series probe is available for the PAL-AT® and LiquidWatch® systems.

General information
Color

Grey/ black

Features

Resettable hydrocarbon probe; Detects hydrocarbon liquids in interstitial spaces of tanks and pipes, sumps and other containment areas; Compact, durable design; Fast respond time; Relay-output capable.

Shape

Cable.

Size

Manufacturer's standard

WarrantyDescription

Consult manufacturer

Uniclass 2015
Pr_75_50_48_67 Probe leak sensorsPrimary
Specification data - Probe leak sensors Enhanced data
Liquid to be detected

Hydrocarbon.

Response time (maximum)

<One minute:

1,1,1, Trichloroethane; acetone; MEK; Xylene; naphtha; gasoline.

<Five minutes:

Diesel fuel; kerosene; jet fuel; crude oil.

Alcohols are not detected.

Resettability

Required.

Exposure limits

Consult manufacturer

Mounting arrangement

Manufacturer's standard

PHLR Probe:

Slips into the end of a 3/4" schedule 40 PVC pipe, which can then be mounted in any orientation, horizontal or vertical.

PHLR-P Probe:

Slips into a 3/4" PVC coupling, which must be mounted vertically.

Product Reference

PHLR Probe

Standard, for non-pressurized applications.

PHLR-P Probe

For pressurized applications.