Verified by manufacturer 2 months ago
100 mm
DoP
Certificate type
Stone wool lamella mat with a reinforced aluminium foil facing.
Suitable for air ducts and other ventilation ducts and equipment.
Thermal and condensation insulation of air ducts and other ventilation ducts and equipment.
Features and benefits:
The surface temperature of the facing must not exceed +80°C (temperature restriction determined in accordance with the heat resistance of adhesive).
PAROC stone wool products are capable of withstanding high temperatures. The binder starts to evaporate when its temperature exceeds approximately 200°C. The insulating properties remain unchanged, but the compressive stress weakens. The softening temperature of stone wool products is over 1000°C.
Color | Silver |
Finish | Foil |
Material | Stone wool |
Uniclass | |
CAWS | U90/490 Site-applied insulation to ductwork U90/490 Site-applied insulation to ductwork |
Form | Lamella mat. |
Thermal conductivity | 0.045 W/m·K at 50°C.Guidance for specification option:
|
Finish | Reinforced aluminium foil facing. |
Fire performance | To EN 14303:2009+A1:2013 (EN 13501-1), Euroclass A1. |
Insulation thickness (minimum) | 100 mm.Manufacturer guidanceTo EN 823: |
Combustibility | To EN ISO 1182:2002, Class 0 according to BS 476: part 6 1989 and part 7 1997. |
Length | 2500 mm. Manufacturer guidanceTo EN 822: |
Water absorption | ≤1 kg/m². |
Thickness tolerance | T4. |
Water vapour diffusion resistance | To EN 14303:2009+A1:2013 (EN 12086), MV2. |
Dimensional stability | To EN 14303:2009+A1:2013 (EN 14706), 500°C. |
Width (nominal) | 1000 mm. Manufacturer guidanceTo EN 822: |
Density | 50 kg/m³. |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |