NBS Source
I'm a manufacturer

OPV Control System

Verified by manufacturer 6 months ago

Colt International Ltd

An intelligent electronic control system which enables the integration of any smoke control components into an addressable smoke control system.

Jump to:
+44 (0)23 9245 1111 Website

Application

Fire safety applications. May also be used to control all manner of natural ventilators, dampers and fans in much the same way as a building management system (BMS).

Description

An intelligent electronic control system which enables the integration of any smoke control components into an addressable smoke control system.

Whilst primarily intended for fire safety applications, it may be used to control all manner of natural ventilators, dampers and fans in much the same way as a building management system (BMS).


Features and benefits:

  • Proven performance: As life safety equipment, all OPV components meet the most stringent manufacturing and test procedures. Its communication network uses the proven and robust Apollo® protocols.
  • Conforming to the latest standards: CE marked for compliance with the Low Voltage Directive and the Electro-magnetic Compatibility Directive.
  • Flexible: Each OPV panel can control up to 126 addressable units per spur with a maximum of four spurs. There is a maximum of ten additional remote firefighter’s override panels (FOPs), each controlling a maximum of 12 control zones.
  • Addressable: Addressability provides flexible control. Each addressable unit can be controlled individually and as part of the specified automatic control system. The control software is configured to suit the automatic scheme requirements and should these change, it is a simple matter of reprogramming the software accordingly.
  • Complete control: Besides the ability to re-configure the system in response to alterations in the scheme, the user can operate the system manually at the display module using the navigation key pad and can amend the daily parameters such as the temperature settings and operating times.
  • Battery backed-up system: OPV offers two independent power sources to operate ventilators. During normal operation the network is powered from the mains, which also charges the integrated battery back-up module. The control system monitors the health of the communications network. The system is so designed that if there is a power failure and no fire signal, all ventilators controlled by the system maintain their current status while the battery supply is healthy. If a fire signal is received during this period, the system will respond as designed.
  • Monitoring and diagnostics: Software and hardware watchdogs detect faults in the system and then act upon these in a logical controlled fashion. These actions extend from merely flagging up an alarm to putting the system into failsafe mode, depending on their severity and the type of system provided. Faults are recorded and can be viewed/ cleared at the display module and they can also be outputted as a signal to a BMS, for example.
  • Low maintenance.
  • Minimal power requirements: Only requires a single phase, 230 V a.c. supply and imposes a 1 amp load. A 3 amp fuse is recommended.
  • Pre-order design service available.

General information

Color

White

Shape

Rectangle

Length

396 mm

Width

316 mm

Height

128 mm

Uniclass

Pr_75_50_18_80 Smoke and heat exhaust control panelsPrimary

Product range

Smoke Control Systems

Specification data - Smoke and heat exhaust control panels

Enclosure

-

Ingress protection (minimum)

Manufacturer's standard.

Material

Manufacturer's standard.

Colour

White.

Nominal voltage

230 V a.c.

Batteries

-

Type

Manufacturer's standard.

Voltage

Manufacturer's standard.

Battery autonomy (stored energy time at rated power)

Manufacturer's standard.

Battery service life (minimum)

Manufacturer's standard.

Mounting

Wall.

Guidance for specification option:

Size (h x w x d):

  • Display panel: 200 x 270 x 48 mm.
  • Heart module: 396 x 316 x 128 mm.

Components

OPV Heart module; OPV display panel.

Guidance for specification option:

  • OPV Heart module: Contains the power supply and intelligence of the overall OPV control system.
  • OPV display panel: The user interface for the Colt OPV system.

Accessories

Expansion module.

Guidance for specification option:

This is an extended I/O for the heart module if there are more than 12 digital inputs or four outputs required.

OPV display extension panel.

Guidance for specification option:

Providing an additional 12 zone indicators.

OPV Firefighter’s Override Panel (FOP).

Guidance for specification option:

Providing an additional point of override facility for the OPV system.