Multi-use pumping system.
The system is suitable for a variety of pumping tasks, ranging from the lifting of sewage from basements to a higher-level sewage system, to the removal of ground water and surface drainage.
Specialist, multi-use pumping system.
Due to the system being modular, the sump chamber is available in a variety of sizes, ranging from 1200–2100 mm high, in increments of 300 mm. With an internal diameter of 830 mm, the sump is large enough to hold 24 hours of storage as required by Building Regulations (Approved Document H).
If the lowest invert is within 300 mm from FFL, the 1500 mm high sump is able to provide 300 L of 24-hour storage which is sufficient for one-bedroom properties. For 450/600 L of storage, the 1800 mm or 2100 mm sump chambers should be used respectively.
Where greater than 24-hour storage is required or where the invert is lower, one of the larger ‘whole house’ pumping systems may be required. Consult manufacturer for details.
Type:
- Pumps for Ground and surface water:
- Pumps for Foul water:
Please Note: For safety reasons, pumps within the 1800 and 2100 mm deep chambers should be on guide rails.
Application:
The system is suitable for a variety of pumping tasks, ranging from the lifting of sewage from basements to a higher-level sewage system, to the removal of ground water and surface drainage.
Features | Specialist, multi-use pumping system, available in a variety of sizes and suitable for a variety of pumping tasks |
Shape | Modular |
Size | 1200 mm, 1500 mm, 1800 mm, 2100 mm (h). Internal diameter of 830 mm |
Uniclass 2015 | |
CAWS | R12/135 Private packaged pumping stations and pressure pipeline system R18/310 Private packaged pumping stations |
Product Reference | Newton BCV-750-65 - P50Newton BCV-750-65 - P51Newton CP400Newton CP750 - P33Newton NP400 - P2Newton NP400 - P3Newton NP750 - P5Newton NP750 - P6Newton SP750 - P36 |
Collection tank capacity (minimum) | 24 hours of storage. Where greater than 24-hour storage is required or where the invert is lower, one of the larger ‘whole house’ pumping systems may be required |
Pumps | - |
Configuration | Modular pumping system |
Impeller | Tungsten carbide tipped cutting impellor for Newton SP750 - P35 and P36 |
Pump characteristic | Medium head and medium performance clean water pumpHigh head and medium performance clean water pumpMedium head and high performance clean water pumpHigh head and high performance clean water pump (ground and surface water)Vortex pump, cutting pump (foul water) |
Non-return valve | Check-valve with at least 60 mm opening for Newton BCV-750-65 - P50 and P51 |
Connections | - |
Inlet diameter | 90 mm |
Height | 1200 mm1500 mm1800 mm2100 mm |
Standard product features | Features: Specialist, multi-use pumping system, available in a variety of sizes and suitable for a variety of pumping tasks. Shape: Modular. Size: 1200 mm, 1500 mm, 1800 mm, 2100 mm (h). Internal diameter of 830 mm. |