The Monodraught Square Sun Tunnel/Sunpipe Kit is designed to provide natural daylight into buildings, for use on flat roofs.
The Monodraught Square Sun Tunnel System is designed for installation onto a flat roof of various building types, including:
The Monodraught Square Sun Tunnel System incorporates a sealed double glazed unit with an outer layer of 3 mm clear float glass, an 8 mm air gap and 3 mm clear float inner glass.
Monodraught Square Sun Tunnels are a way to harness natural daylight from rooftops into interiors to brighten dark rooms and underground spaces. The Monodraught sun pipes are suited to almost any application, and have been installed anywhere from residential bedrooms to large commercial properties.
All Monodraught sunpipe systems are guaranteed for ten years.
Smaller sizes have a recommended total maximum pipe length of 8 m. Larger sizes allow for longer lengths to be used. There is a 12% reduction of light output for each 45° bend used and there is a 6% reduction in light transmission for every metre of SUNPIPE.
30° & 45° adjustable elbows can be used with all SUNPIPE applications to direct daylight to where it is required.
Features and benefits:
Components:
Color | White |
Finish | Mirrored Guidance for specification option: Pipe. |
Material | Aluminium Guidance for specification option: Pipe. |
Shape | Square |
Length | 300 mm 450 mm |
Width | 300 mm 450 mm |
Warranty description | Ten year |
Uniclass | |
CAWS | L10/495 Daylight pipe |
Product range |
Material | Aluminium.Guidance for specification option: Anodized aluminium tube; double glazed ceiling diffuser. |
Internal finish | Micro silver 27/427OAG. |
Diameter | 300 mm.Manufacturer guidancePipe diameter. |
Bends | 45°.Adjustable. |
Accessories | Roof flashings. |
Dimensions | 300 x 300 mm (12 x 12"). Guidance for specification option: Can light an area of 14 m². |
Pipe extensions | Not required. Guidance for specification option: If pipe length is not required to be longer than 1200 mm. One. Guidance for specification option: For pipe lengths of 1200–1800 mm. Two. Guidance for specification option: For pipe lengths of 1800–2400 mm. Three. Guidance for specification option: For pipe lengths of 2400–3000 mm. Four. Guidance for specification option: For pipe lengths of 3000–3660 mm. |
FrameSize | 480 x 580 mm. Manufacturer guidanceRoof frame size. |
Openings | 500 x 600 mm. Manufacturer guidanceRoof opening. |
Inner layer | 3 mm clear float glass. |
Spacer | 8 mm air gap. |
Outer | 3 mm clear float inner glass. |
Opening | 320 x 320 mm. Manufacturer guidanceRequires ceiling opening. |
Material | Aluminium Guidance for specification option: Pipe. |