Verified by manufacturer 13 days ago
XRGI®6 without condensing technology
ISO 9001 Quality Management
Certificate type
Modulating combined heat and power (CHP) units.
Suitable for communal heating systems and commercial buildings with simultaneous heat and electricity demand.
The XRGI® is a combined heat and power plant (CHP) that works on the principle of co-generation. In addition, it can also be extended with thermal storage to optimise operation.
High efficiency CHP unit with maximum rating of 20 kW(e)/ 40 kW(th). Can modulate down to 50% load.
Features and benefits:
Color | Blue |
Finish | Painted |
Shape | Rectangle |
Length | 930 mm 1120 mm |
Width | 640 mm 750 mm |
Height | 960 mm 1170 mm |
Warranty description | Two year |
Uniclass | |
CAWS | T90/110 Heating system |
Prime mover | |
Standard | To EN 50465. |
Engine type | Gas engine. |
Electrical generator | |
Standard | To ISO 8528-13:2016. |
Type | Asynchronous. |
Operation | Three phase, 400 V, 50 Hz. |
Output | |
Electrical power | 6.0 kW. |
Thermal power | 12.4 kW. |
Efficiency | |
Electrical | 30.1%. |
Thermal | 62.3%. |
Overall | 92.4%. |
Components | Power Unit, iQ20s Control Panel, Q20-Heat Distributor. |
Control systems | |
Enclosure | |
Mounting position | Wall mounted. |
Protection | 32 A. |
User interface | LCD screen with push-button operation. |
Functions | Manufacturer's standard. |
Communications interface | VFC.MODBUS RS485.GSM. |
Ancillary components | Temperature sensors, current transformers, reference meter. |
Monitoring | |
Display the following conditions | |
Electrical properties | G98/G99 current transformers to measure building load. |
Heat exchanger | Flow and return temperature. |
Alarms | |
Engine | Run, standby, fault, fault code. |
Accessories | Not required.Flow master including flow master control without condensing technology - FM 50.Flow master including flow master control without condensing technology - FM 150.Flow master including flow master control without condensing technology - FM 250.Flow master including flow master control without condensing technology - FM 350.Manufacturer guidanceConsult manufacturer and insert requirements or omit. |
Overall sound power level | 63 dB. |
Country of product manufacture | Denmark |
Manufacturing plant location |
Platform | Compatible | Version |
---|---|---|
- | 1 |