LI TE – Indoor

Description

The LI range of internal air source heat pumps has seven models with heating outputs ranging from 11–40 kW. The LITES units are designed for indoor installation on an external wall or in a corner, making them ideal for installations where it is not practical to install an external unit.

Features and benefits:

  • Configurable for corner or wall installation using air ducts for the air intake and the air outlet (supplied by installer). Dimplex rain guards are available as an accessory.
  • Two compressors for output regulation when operating at partial load (LI20–40TES only).
  • Capable of flow temperatures up to 60°C with high COP due to an evaporator optimized for heating operation and energy-efficient reverse cycle defrost. Reduced noise due to sound-optimized axial fan and vibration-isolated compressor.
  • Supplied with integrated WPM2007 plus controller heat pump manager which can be wired as a remote control using the optional MSPGD wall mounting set. Compatible with BMS system or Ethernet network with an additional accessory.
  • Integrated flow and return sensor, dirt trap and flow rate sensor. External NTC-2 sensor included in the scope of supply.

General information

Uniclass 2015

Pr_70_60_37_04 Air-to-water heat pumpsPrimary

CAWS

T90/505 Air-to-water heat pumps

Specification data - Air-to-water heat pumps

Product Reference

LI TE – Indoor

Type

LI11TES

Nominal power consumption at A7/ W35: 2.4 kW. Size (w x h x d): 750 x 1360 x 880 mm.

LI16TES

Nominal power consumption at A7/ W35: 4.1 kW. Size (w x h x d): 750 x 1570 x 880 mm.

LI20TES

Nominal power consumption at A7/ W35: 4.5 kW. Size (w x h x d): 750 x 1570 x 880 mm.

LI24TES

Nominal power consumption at A7/ W35: 6 kW. Size (w x h x d): 750 x 1710 x 1030 mm.

LI28TES

Nominal power consumption at A7/ W35: 7.9 kW. Size (w x h x d): 750 x 1710 x 1030 mm.

LI40AS

Nominal power consumption at A7/ W35: 8.1 kW. Size (w x h x d): 1735 x 2100 x 952 mm.

Standard product features

Technical characteristics:

  • Maximum flow temperature: 60°C. (58°C for LI40AS).
  • Air operating limits: -20 to +35°C.
  • Sound power level: 53–64 dB (A), model dependant.
  • Sound pressure level at 10 m: 48–60 dB (A), model dependant.
  • Refrigerant: R410A, except LI40AS which uses R404A.
  • Heating water flow rate/ Pressure drop: 1.4–6.3 m³/h / ≥ 15 300 Pa, model dependant.
  • Heat flow rate (minimum): 2800–9500 m³/h, model dependant.
  • Rated voltage: Three phase, 400 V, 50 Hz.
  • Fuse protection: C 10–25 A, model dependant. (Fuse and cable to be determined in accordance with BS 7671).
  • Air duct connection: Varies depending on model, consult literature for details.
  • Reverse circulation defrosting.
  • ERP rating: A++.

Heat output, one compressor (in accordance with EN 14511):

- LI11TES:

  • A-7/ W35 (COP A-7/ W35): 7.00 kW / 3.00.
  • A2/ W35 (COP A2/ W55): 8.28 kW / 3.60.
  • A7/ W35 (COP A7/ W35): 10.00 kW / 4.20.
  • A10/ W35 (COP A10/ W35): 11.10 kW / 4.70.

- LI16TES:

  • A-7/ W35 (COP A-7/ W35): 10.70 kW / 2.70.
  • A2/ W35 (COP A2/ W55): 13.40 kW / 3.30.
  • A7/ W35 (COP A7/ W35): 16.40 kW / 4.00.
  • A10/ W35 (COP A10/ W35): 17.70 kW / 4.40.

- LI20TES:

  • A-7/ W35 (COP A-7/ W35): 6.90 kW / 2.90.
  • A2/ W35 (COP A2/ W55): 8.70 kW / 3.40.
  • A7/ W35 (COP A7/ W35): 10.50 kW / 4.10.
  • A10/ W35 (COP A10/ W35): 11.50 kW / 4.50.

- LI24TES:

  • A-7/ W35 (COP A-7/ W35): 8.30 kW / 2.60.
  • A2/ W35 (COP A2/ W55): 10.50 kW / 3.20.
  • A7/ W35 (COP A7/ W35): 12.40 kW / 3.70.
  • A10/ W35 (COP A10/ W35): 13.40 kW / 3.90.

- LI28TES:

  • A-7/ W35 (COP A-7/ W35): 11.40 kW / 2.60.
  • A2/ W35 (COP A2/ W55): 13.40 kW / 3.10.
  • A7/ W35 (COP A7/ W35): 14.50 kW / 3.20.
  • A10/ W35 (COP A10/ W35): 15.10 kW / 3.40.

- LI40AS:

  • A-7/ W35 (COP A-7/ W35): 13.50 kW / 3.10.
  • A2/ W35 (COP A2/ W55): 16.80 kW / 3.90.
  • A7/ W35 (COP A7/ W35): 20.00 kW / 4.60.
  • A10/ W35 (COP A10/ W35): 21.70 kW / 4.90.

Heat output, two compressors (in accordance with EN 14511):

- LI20TES:

  • A-7/ W35 (COP A-7/ W35): 12.80 kW / 2.90.
  • A2/ W35 (COP A2/ W55): 14.70 kW / 3.30.
  • A7/ W35 (COP A7/ W35): 17.70 kW / 4.00.
  • A10/ W35 (COP A10/ W35): 20.70 kW / 4.50.

- LI24TES:

  • A-7/ W35 (COP A-7/ W35): 15.67 kW / 2.70.
  • A2/ W35 (COP A2/ W55): 19.90 kW / 3.40.
  • A7/ W35 (COP A7/ W35): 23.40 kW / 3.90.
  • A10/ W35 (COP A10/ W35): 24.80 kW / 4.10.

- LI28TES:

  • A-7/ W35 (COP A-7/ W35): 21.63 kW / 2.80.
  • A2/ W35 (COP A2/ W55): 25.20 kW / 3.30.
  • A7/ W35 (COP A7/ W35): 27.80 kW / 3.50.
  • A10/ W35 (COP A10/ W35): 28.30 kW / 3.60.

- LI40AS:

  • A-7/ W35 (COP A-7/ W35): 23.80 kW / 3.00.
  • A2/ W35 (COP A2/ W55): 29.30 kW / 3.80.
  • A7/ W35 (COP A7/ W35): 35.70 kW / 4.40.
  • A10/ W35 (COP A10/ W35): 38.10 kW / 4.70.

Literature

B. Renewable Heat

B. Renewable Heat

Third party certifications

  • CE