Verified by manufacturer 5 months ago
BBA Agrément Certificate
Certificate type
Torch-applied high performance SBS elastomeric membrane warm and cold roof system.
Torch applied, high performance styrene-butadiene-styrene (SBS) elastomeric membrane warm and cold roof system for flat or sloping roofs.
Features and benefits:
Components:
Color | Manufacturer guidanceMultiple colour selections available. |
Finish | Textured Guidance for specification option: Slip-resisting slate granule surface. |
Material | Bitumen Guidance for specification option: SBS elastomeric bitumen. |
Warranty description | 30 year Guidance for specification option: Independently insured guarantee for materials and workmanship. |
Uniclass | |
CAWS | J41/10 Reinforced bitumen membrane warm deck roof covering J41/110 Built-up reinforced bitumen membrane warm deck roof covering |
Product range |
Preparation | |
Horizontal work | Langley Spray-On Primer. |
Skirtings and vertical work | Langley Spray-On Primer. |
Air and vapour control layer | |
Type | Parevapo SBS (3.8 kg/m²). |
Attachment | Torch-bonded. |
Insulation | |
Type | Parafoam Ultra PIR Insulation (3.84 kg/m²). |
Waterproof covering | |
First layer | |
Type | Adepar JS (3.6 kg/m²). |
Attachment | Attached via self-adhesive strips. |
Top layer | |
Type | Parafor Solo GS (5.71 kg/m²). |
Attachment | Torch-bonded. |
Colour | Guidance for specification option: Available in several colours, consult manufacturer and insert requirements. |
Weight | 16.95 kg/m². Guidance for specification option: Based on 120 mm insulation thickness. |
Resistance class | Resistance class (to MOAT 31): R4. |
Vapour control layer | 3 mm. |
Insulation | 120 mm. |
Basecoat | 3 mm. |
Top coat | 5 mm. |
Overall thickness | 131 mm. |
Fire performance | Fire performance: Broof [t4]. Guidance for specification option: To BS EN 13501-5:2016. |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
Revit 2017 | 1 | |
- | 1 |