NBS Source
I'm a manufacturer
Compare variants

Knauf Performer with Knauf Resilient Bar: PC-RB1-70-055-6-2-15-SSP-50

Verified by manufacturer 2 months ago

With deflection head arrangement

Knauf UK Variant:
Third party certifications:
  • EPD

    EPD

    Certificate type

  • CCPI System

    CCPI System

    Certificate type

The Knauf Performer system is Knauf's most versatile and commonly used partition system.

Jump to:
0800 521 050 Website

Application

Plasterboard partition system with resilient bar.

Description

The Knauf Performer system is Knauf's most versatile and commonly used partition system. It is constructed using a single row of Knauf metal studs with Knauf plasterboards to both sides in order to meet fire, acoustic, moisture and impact requirements.

The Performer system is lightweight, simple to construct and should be used in conjunction with Knauf’s finishing solutions range.


Knauf Resilient Bar can be added to both or one side of certain Knauf Performer systems. This additional component improves the acoustic sound reduction performance of the system in order to meet higher acoustic requirements.

General information

Material

Gypsum

Metal

Glass mineral wool

Shape

Rectangle

Other

Square

Width

Bespoke

Height

Bespoke

Uniclass

Ss_25_10_30_35 Gypsum board partition systemsPrimary

CAWS

K10/30 Metal stud

K10/125 Metal stud partition system

Product range

Internal Walls & Partitions / Knauf Performer with Knauf Resilient Bar (Partitions)

Specification data - Gypsum board partition systems

Framing

Knauf 70 'C' (0.55) at 600 mm centres to suit maximum height.
Head channel: Knauf 72 Deep Flange 'U' Channel (0.70) (70 mm deep flange).
Floor channel: Knauf 72 'U' Channel (0.55).
Knauf Resilient Bar fixed to one side at 600 mm centres across the stud frame.

Insulation

50 mm Knauf Insulation Acoustic Roll.

Linings

2 x 15 mm Knauf Soundshield Plus to each side.

Fasteners

Inner layer: 25 mm Knauf Performance Plus screws.
Outer layer: 45 mm Knauf Performance Plus screws.

Joint treatment

Horizontal joint: Knauf Flat Fixing Plate (to be applied behind outer layer plasterboard).

Finish

System must be taped and jointed using Knauf Joint Filler (Premium) or Knauf Joint Cement Premium and Knauf Joint Tape (Paper). Or alternative Knauf jointing compounds manufactured to EN 13963.
Knauf Wallboard Primer applied once taping and jointing completed.
Prior to where paint decoration is required. For preparation for decoration of where gypsum plaster skim is required, the outer layer of plasterboard joints is required to be taped and filled, using Knauf Joint Filler (Premium) and Knauf Joint Tape (Paper) meeting quality level 1 in accordance with Eurogypsum - Drywall Jointing & Finishing - Surface quality level classification.
For application where gypsum skim finish is required, the Knauf system is to be taped and filled using Knauf jointing compounds.

Execution

Consult manufacturer's literature at
https://www.knauf.co.uk/our-services/resources

Deflection head

For deflection head allowance of up to -25 mm or ±12.5 mm: use 2 x 19 mm Knauf Coreboard fillets.

Manufacturer guidance

The fire resistance performance of the system is based on tested solutions using deflection head construction.

Fire resistance

EI 60 tested in accordance with BS EN 1364-1.

Sound insulation

60 dB (Rw) when tested to BS EN 10140-2.
55 dB (Rw + Ctr) when tested to BS EN 10140-2.

Duty rating (to BS 5234-2)

Severe Duty in accordance with BS 5234-2, clause 1.6.2 & 1.6.3 of Annex B & C.

System code

EN-PC-RB1-70-055-6-2-15-SSP-50.

Guidance for specification option:

The maximum height stated (see Partition height) is for the fire resistance of the system to meet project requirements where EN compliance is required. The stated maximum height figure is the lower value between the cold state height, calculated structurally to a limiting deflection of L/240 @ 200 Pa and the fire state height, as outlined in accordance with EN 1364-1.

BS-PC-RB1-70-055-6-2-15-SSP-50.

Guidance for specification option:

The maximum height stated (see Partition height) is for the fire resistance of the system to meet project requirements where BS compliance (BS 476-22), is required and is accepted by the client, designers and building control. The stated maximum height figure is based on the maximum cold state height, calculated structurally to a limiting deflection of L/240 @ 200 Pa.

Partition height

-

Manufacturer guidance

Insert requirements.

  • EN-PC-RB1-70-055-6-2-15-SSP-50: Maximum height: 3000 mm.
  • BS-PC-RB1-70-055-6-2-15-SSP-50: Maximum height: 4200 mm.


See also System code for further details.

Partition thickness

148 mm.

Manufacturer guidance

Excluding finishes.

Sustainability data

Country of material origin

Spain

Manufacturer guidance

Applies to our natural gypsum only which is the main component of plasterboard. Other components are from other countries. Please contact Knauf for more details.

Country of product manufacture

United Kingdom

Manufacturer guidance

UK applies to the majority of manufacture but a small percentage of finished items may be imported. Please contact Knauf for more details.

Material

Gypsum

Metal

Glass mineral wool

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

-

Manufacturer guidance

Individual product EPDs for plasterboard and metal components available at: https://www.knauf.co.uk/our-services/resources/environmental-product-declarations-1

Recyclability

Individual product EPDs for plasterboard and metal components available at: https://www.knauf.co.uk/our-services/resources/environmental-product-declarations-1

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

11.9 %

Manufacturer guidance

(2023 average by mass for all UK produced plasterboards, recycled gypsum & paper)

Third party certifications

Third party certifications

EPD

EPD

Knauf Coreboard EPD

EPD

EPD

Knauf Internal Metal Partition Components EPD

EPD

EPD

Knauf Soundshield Plus EPD

EPD

EPD

Knauf Insulation Acoustic Roll 50mm EPD

CCPI System

CCPI System

CCPI Assessment Certificate

Literature

Knauf Soundshield Plus Data Sheet

Knauf Soundshield Plus Data Sheet

Knauf Core Board Data Sheet

Knauf Core Board Data Sheet

Knauf C Stud Data Sheet

Knauf C Stud Data Sheet

Knauf DF U Channel Data Sheet

Knauf DF U Channel Data Sheet

Knauf Intumescent and Acoustic Mastic Data Sheet

Knauf Intumescent and Acoustic Mastic Data Sheet

Knauf U Channel Data Sheet

Knauf U Channel Data Sheet

Knauf Flat Fixing Plate Data Sheet

Knauf Flat Fixing Plate Data Sheet

Knauf Performance Plus Screws Data Sheet

Knauf Performance Plus Screws Data Sheet

Knauf Paper Joint Tape Data Sheet

Knauf Paper Joint Tape Data Sheet

Knauf Fill and Finish Light Data Sheet

Knauf Fill and Finish Light Data Sheet

Knauf Insulation Acoustic Roll Data Sheet

Knauf Insulation Acoustic Roll Data Sheet

Knauf Resilient Bar Data Sheet

Knauf Resilient Bar Data Sheet

Knauf Wafer Head Self Tapping Screw Data Sheet

Knauf Wafer Head Self Tapping Screw Data Sheet

Knauf EN Compliance Systems

Knauf EN Compliance Systems

Knauf BS Compliance Systems

Knauf BS Compliance Systems

Knauf Fire Rated Deflection Heads Document

Knauf Fire Rated Deflection Heads Document

Knauf Standard Details - Performer Double Boarded

Knauf Standard Details - Performer Double Boarded

The 100% Knauf System Performance Warranty

The 100% Knauf System Performance Warranty

Knauf Specification Disclaimer

Knauf Specification Disclaimer