Energy efficient, lightweight pre-insulated rectangular HVAC ductwork system with low air leakage. Fabricated with premium performance Kingspan KoolDuct® phenolic panels.
The Kingspan KoolDuct System of pre-insulated ductwork is designed for use in building services / HVAC applications. It is suitable for both new build and residential, commercial, public, light industrial and leisure sectors.
Designed for mechanical ventilation, heating and air-conditioning systems, The Kingspan KoolDuct System is suitable for both new build and refurbishment projects in the residential, commercial, public, light industrial and leisure sectors. Moreover, it is especially suitable for use in nonferrous applications such as MRI scanning units in hospitals, and on other high specification projects where non-fibrous insulants may be preferred.
Ductwork design and frictional resistance:
Kingspan KoolDuct rectangular ductwork, including fittings, follows the same calculation principles and duct sizing methods as are used for rectangular metal ductwork.
The frictional resistance is comparable with that of galvanized sheet steel ductwork.
Features and benefits:
Operational limits:
The recommended operational limits for ductwork fabricated from the Kingspan KoolDuct® System:
Standards:
- Quality Control:
Kingspan KoolDuct panels are manufactured to the highest standards under a management system certified to:
Sustainability:
The insulation core of Kingspan KoolDuct® panels is manufactured with a CFC / HCFC-free blowing agent that has very low Ozone Depletion Potential (ODP) and low Global Warming Potential GWP < 5.
BREEAM – ductwork fabricated from The Kingspan KoolDuct® System can contribute directly, and indirectly, toward the achievement of credits in the building rating system, BREEAM. The relevant credits are Ene1 – Reduction of energy use and carbon emissions Mat 1 – Life Cycle Impact, Mat 3 – Responsible sourcing of materials.
Color | Grey Pink |
Finish | Foil |
Material | Phenolic foam |
Shape | Other |
Length | 2950 mm |
Width | 1200 mm |
Height | 22 mm 30 mm |
Uniclass | |
CAWS | U90/670 Rigid ductwork generally U90/425 Rigid ductwork and fittings |
Product range |
Standard | To BS EN 13403. |
Insulation material | Phenolic foam (PF). |
Internal and external material | Phenolic insulation is covered by factory-applied aluminium foil facings on both sides. |
Finish | Aluminium foil facing. |
Accessories | |
Material | Compatible with ductwork. |
Finish | To match ductwork. |
Access openings | |
Purpose | Inspection. |
Sizes | To BS EN 12097. |
Execution | Air ductwork generally. |
ThermalConductivity | 0.023 W/m·K at -20°C, 0.022 W/m·K at 10°C, 0.023 W/m·K at 19°C, 0.024 W/m·K at 25°C, 0.027 W/m·K at 50°C, 0.031 W/m·K at 80°C. |
Standard | BS EN ISO 9001: 2015 (Quality Management Systems. Requirements), BS EN ISO 14001: 2015 (Environmental Management Systems. Requirements), BS ISO 45001: 2018 (Occupational health and safety management systems) and |
Insulation thickness (minimum) | 30 mm. |
Vapour barrier material | Factory-applied aluminium foil (standard for indoor use) vapour .barrier facing |
Protection | If the duct system is to the external of the building it has to be protected by one of the following: aluminium sheet, aluminium–zinc alloy coated steel sheet, heavy-duty self-adhesive laminate, reinforcing glass/ synthetic cloth embedded between two coats of appropriate coating or UV resistant glass reinforced polyester/ epoxy (GRP/ GRE). |
Accessories | For duct assembly: Either tiger clips or adhesive, aluminium foil tape and silicone sealant. Flanges/ couplings: tiger clips or 4-bolt flange/ aluminium grip flange with bayonet cleat. Reinforcements / stiffners: Tie rods/Reinforcing bars. |
Reaction to fire classification | Euroclass B-s1,d0 exposed foil side and C-s2,d0 non-exposed foil side. |
FM approved | No (not applicable to pre-insulated ductwork for HVAC application). |
Compressive strength (minimum) | >175 kPa at 10% compression. |
Closed cell content | ≥90%. |
Nominal density range | 55–60 kg/m³. |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Material | Phenolic foam |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 3.36 kg CO₂ eq/kg Manufacturer guidance1 m² of insulation at a thickness that gives an R-value of 3.000 m².K/W (66mm) gives a GWP of 13.3 kg CO2 equivalent per functional unit, in Life cycle stages A1 - A3 (Raw material supply, transport and manufacturing). For KoolDuct this is equivalent to 3.36 kg CO2e/kg |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |