NBS Source
KESSEL Staufix Control
Compare variants

KESSEL Staufix Control

Twin flap backwater valve - concrete/slab floor, 110Ø, tileable cover, telescopic upper

IPS Flow Systems Variant:

Backwater valves for wastewater without sewage, with additional control functions.

Jump to:
+44 (0)191 521 3111 www.ipsflowsystems.com

Application

Anti-flood valve, for installation in concrete slabs/ floors or exposed wastewater pipes.

Description

Backwater valves for wastewater without sewage, with additional control functions.


Features and benefits:

  • Provides the same safe and reliable protection against backwater as the Staufix (specified separately).
  • Can be installed in in concrete slabs/ floors or exposed wastewater pipes.
  • Concrete slab/ floor variants include a telescopic upper section for continuous height and level adjustment, a surface-water-tight cover plate class A 15 made of polymer and an installation kit with choice of cover.
  • Includes two self-closing flaps, one of which can be locked by hand as an emergency closure.
  • Equipped with a remote signal generator which emits both a visual and acoustic warning signal when backwater occurs.
  • With the optional wireless receiver as a switchable socket, a washing machine, for example, could be automatically turned off to prevent it from pumping water into a blocked sewer pipe.
  • Tool-free maintenance: Quick-fastening, single-hand closure system with lift function, the cover is particularly easy to open and close.
  • Available with or without rodent protection.


Available without alerts; see Staufix Basic (specified separately).

General information

Color

Black

Material

Polymer

Stainless steel

Uniclass

Pr_65_54_24_04 Anti-flood valvesPrimary

CAWS

R11/11 Plastics branch pipework

R12/355 Antiflood valves

Specification data - Anti-flood valves Enhanced data

Standard

To BS EN 13564-1.

Classification

Type 2.

Form

For installation depth 287–410 mm.

Installation area: 750 x 750 mm.

See manufacturer's literature for detailed dimensions.

For installation into concrete slab/ floor; without rodent protection.

Two polymer self-closing flaps.

770 100.10X

For installation into concrete slab/ floor; with rodent protection.

One polymer self-closing flap, one stainless steel self-closing flap.

770 100.10XR

Material

Polymer.

Rodent protection variants include a stainless steel flap.

Consult manufacturer for details.

Connections

Outer diameter: 110 mm.

Integral accessories

None.

Radio-based audible alarm.

For forwarding a visual and acoustic signal in the event of backwater.

Radio receiver as switched socket.

For killing power in the event of backwater (e. g. washing machine).

Extension section with flange (deeper installation).

Polymer section with inclusive sealing.

Maximum extension: 147 mm.

Extension section with flange and counter flange (deeper installation).

Polymer section with stainless steel counter flange and inclusive sealing. For connection to on-site membrane.

Maximum extension: 147 mm.

Extension section with flange (waterproof concrete).

Elastomer waterproofing membrane, made of NK/SBR, 700 mm diameter. Suitable for installation in concrete slab/ floor.

Maximum extension: 294 mm.

Supplied completely assembled.

Lockable cover.

Spigot.

Diameter to match outer diameter specified above.

Removeable fitting, mountable on both sides and in different dimensions.

Socket.

Diameter to match outer diameter specified above.

Removeable fitting, mountable on both sides and in different dimensions.

Similar products from IPS Flow Systems

KESSEL Drehfix Basement Drain

KESSEL Drehfix Basement Drain

KESSEL Ecolift XL Backwater Pumping Station 4 L/s to 20 L/s - Complete Unit (Minimum Installation Height)

KESSEL Ecolift XL Backwater Pumping Station 4 L/s to 20 L/s - Complete Unit (Minimum Installation Height)

KESSEL Ecolift XL Backwater Pumping Station 4 L/s to 20 L/s - System Base for use with Engineering Chambers

KESSEL Ecolift XL Backwater Pumping Station 4 L/s to 20 L/s - System Base for use with Engineering Chambers

KESSEL Multitube

KESSEL Multitube

KESSEL Pumpfix F Backwater Pumping Station up to 4 L/s

KESSEL Pumpfix F Backwater Pumping Station up to 4 L/s

KESSEL Staufix Basic

KESSEL Staufix Basic

KESSEL Staufix FKA

KESSEL Staufix FKA

KESSEL Staufix Ø 50 and Ø 75

KESSEL Staufix Ø 50 and Ø 75

KESSEL Staufix SWA

KESSEL Staufix SWA

KESSEL System Chamber 1000Ø - 600Ø Opening

KESSEL System Chamber 1000Ø - 600Ø Opening