High performance Ultimate™ slab for fire protection of rectangular ductwork.

Jump to:
+44 (0) 800 0322 555 Website

Application

HVAC - Fire Protection of Ductwork

Description

Isover U Protect Slab 4.0 Alu1 is a lightweight and easy to install Ultimate™ mineral wool slab. It combines all the advantages of conventional thermal and acoustic insulation with Euroclass A1 fire classification and is a component of the Isover U Protect System.

The Isover U Protect system has been tested in accordance to EN 1366-1 and EN 1366-8 and assessed against the criteria in BS 476: Part 24. It offers up to 2 hours passive fire protection in HVAC ventilation and smoke extract ducts as well as up to 1 hour passive fire protection for kitchen ducts.

The fire resistance is also dependent on the application, thicknesses of insulation and the method of installation.

Please contact isover.technical@saint-gobain.com for further details.

Product Features:

  • Ultimate™ mineral wool 600 x 1200mm slab with a black aluminium foil facing.
  • Supplied in 30-100mm thicknesses.

Fire Classification:

Euroclass A1 Reaction to Fire classification according to EN 13501-1

Product Benefits:

  • Fire Protection - The Isover U Protect system has been tested in accordance to EN 1366-1 and EN 1366-8 and assessed against the criteria in BS 476: Part 24. It offers up to 2 hours passive fire protection in HVAC ventilation and smoke extract ducts as well as up to 1 hour passive fire protection for kitchen ducts.1
  • Ease of Install - The Ultimate™ slabs offer a lightweight solution compared to traditional stone wool options, ensuring ease of handling and installation, as well as reducing the stress on supporting structures. Their flexibility and mechanical strength allows fast and efficient cutting and fitting. The adhesive used in the system is only required at penetration details rather than at every insulation joint.
  • Fire Classification - Achieves a Euroclass A1 Reaction to Fire classification, according to EN 13501-1.
  • Thermal Performance - Offers energy savings through helping to control temperatures and reduce heat loss or gain within ductwork.
  • Acoustic Benefits - The inherent sound deadening properties of the Ultimate™ mineral wool insulation will help to reduce noise from ductwork, improving the acoustic comfort of those living or working within the building.  

1 Fire resistance is dependent on the application, thicknesses used and method of installation.

The system includes a range of accessories (intumescent paint, glue, screws and tape) to ensure the correct installation of the Isover U Protect system. For further details, please visit isover.co.uk/hvac-insulation/duct-insulation-fire-protection or contact isover.technical@ saint-gobain.com.

Key Considerations:

When using Isover U Protect Slab 4.0 Alu1, you need to satisfy yourself that use of the product meets all relevant national Building Regulations and guidance as well as local, national and other applicable standards relevant for your construction or application, including requirements in relation to fire.

Please refer to the following product documents:

  • Product Datasheets
  • Declaration of Performance
  • Safe Use Instruction Sheet

General information

Color

Black

Yellow

Finish

Other

Material

Mineral wool

Shape

Rectangle

Length

1200 mm

Width

600 mm

Uniclass

Pr_80_77_76_53 Mineral wool duct slab insulationPrimary

CAWS

T90/450 Insulation to pipelines to control heat loss

T90/450 Insulation to pipelines to control heat loss

Specification data - Mineral wool duct slab insulation

Standard

To EN 14303.

Form

Flexible slabs.

Thermal conductivity

0.031–0.096 W/m.K (10–400°C).

Guidance for specification option:

  • 0.031 W/m.K at 10°C.
  • 0.035 W/m.K at 50°C.
  • 0.040 W/m.K at 100°C.
  • 0.047 W/m.K at 150°C.
  • 0.054 W/m.K at 200°C.
  • 0.072 W/m.K at 300°C.
  • 0.096 W/m.K at 400°C

Finish

Aluminium foil faced.

Fire performance

Euroclass A1 Reaction to Fire classification according to EN 13501-1.

Insulation thickness (minimum)

30 mm.

40 mm.

50 mm.

60 mm.

70 mm.

80 mm.

90 mm.

100 mm.

Execution

Installing foil faced mineral wool insulation on ductwork.

Sustainability data

Material

Mineral wool