NBS Source
I'm a manufacturer

Isover U Protect Accessories

Verified by manufacturer 7 months ago

Saint-Gobain Insulation UK

The Isover U Protect Accessories range, consisting of intumescent paint, glue, screws and tape, is integral to ensuring the correct installation of the Isover U Protect system.

Jump to:
+44 (0) 800 0322 555 Website

Application

HVAC - Fire Protection of Ductwork

Description

The U Protect system has been tested in accordance to EN 1366-1 and EN 1366-8 and assessed against the criteria in BS 476: Part 24. It offers up to 2 hours passive fire protection in HVAC ventilation and smoke extract ducts as well as up to 1 hour passive fire protection for kitchen ducts.


The fire performance of the system cannot be substantiated if alternative system components are substituted.


  • Protect Black Tape - self-adhesive black aluminium tape for covering the insulation slab edges for rectangular ducts.
  • Protect BSF Intumescent Paint - used for sealing all penetrations - solvent free and pH neutral, white aqueous intumescent dispersion
  • Protect BSK Adhesive - Non-combustible, inorganic adhesive based on alkaline sodium silicate for gluing the insulation to the wall, floor or ceiling. It is only required at penetration details rather than at every insulation joint.
  • Fire Protect Screws - spiral shaped screws made of galvanised steel to fix U Protect Slabs on rectangular ductwork


The fire resistance is also dependent on the application, thicknesses of insulation and the method of installation.

Please contact isover.technical@saint-gobain.com for further details.


Key Considerations

When using Isover U Protect Wired Mat 4.0 Alu1, you need to satisfy yourself that use of the product meets all relevant national Building Regulations and guidance as well as local, national and other applicable standards relevant for your construction or application, including requirements in relation to fire.


Please refer to the following product documents:

  • Product Datasheet
  • Protect BSK Adhesive safe Use Instruction Sheet
  • Protect BSF Intumescent Paint Safety Data Sheet

General information

Color

Other

Finish

Other

Material

Other

Guidance for specification option:

  • Galvanised steel 
  • Aluminium

Uniclass

Pr_80_77_76_54 Mineral wool pipe section insulationPrimary

CAWS

U90/490 Site-applied insulation to ductwork

U90/490 Site-applied insulation to ductwork

Specification data - Mineral wool pipe section insulation

Thermal conductivity

Guidance for specification option:

  • 0.031 W/m.K at 10°C.
  • 0.035 W/m.K at 50°C.
  • 0.040 W/m.K at 100°C.
  • 0.047 W/m.K at 150°C.
  • 0.054 W/m.K at 200°C.
  • 0.072 W/m.K at 300°C.
  • 0.096 W/m.K at 400°C.


Accessories

Manufacturer's standard.

Guidance for specification option:

A full range of accessories is available to help ensure effective fire protection and straightforward installation.

Sustainability data

Material

Other

Guidance for specification option:

  • Galvanised steel 
  • Aluminium