NBS Source
I'm a manufacturer

Application

  • HVAC - Ductwork

Description

CLIMCOVER Roll Alu2 can be considered for the thermal and acoustic insulation of circular metal ductwork. The strong, flexible and lightweight glass mineral wool rolls are easy to handle and feature an aluminium foil facing, which provides an inherent vapour barrier and a professional finish.


Product Features

  • 1.2m wide glass mineral wool roll with an aluminium foil facing
  • Supplied in 25-50mm thicknesses
  • Manufactured from up to 82% recycled glass.
  • Achieves Eurofins Gold certification, the highest accreditation for indoor air quality


Fire Classification

Euroclass A2-s1,d0 Reaction to Fire classification according to EN 13501-1.


Product Benefits

  • Thermal Performance - Offers energy savings through helping to control temperatures and reduce heat loss or gain within ductwork.
  • Easy to Install - Lightweight and offers a combination of flexibility and mechanical strength, allowing fast and efficient cutting and fitting.
  • Acoustic Benefits - The fibre structure of glass mineral wool traps sound energy and dissipates it within its thickness, helping to improve the acoustic comfort of those living or working within the building.
  • Fire Classification - Achieves a Euroclass A2-s1,d0 Reaction to Fire classification, according to EN 13501-1.
  • Sustainability - Manufactured from up to 82% recycled glass on a plant that uses 100% renewable electricity. For further details visit insulation-uk.com/CSR


Key Considerations

When using Isover CLIMCOVER Roll Alu2, you need to satisfy yourself that use of the product meets all relevant national Building Regulations and guidance as well as local, national and other applicable standards relevant for your construction or application, including requirements in relation to fire.


Please refer to the following product documents:

  • Product Datasheet
  • Declaration of Performance
  • Safe Use Instruction Sheet

General information

Color

Silver

Guidance for specification option:

Face

Yellow

Finish

Foil

Material

Glass mineral wool

Guidance for specification option:

Glass

Width

1200 mm

Uniclass

Pr_80_77_76_54 Mineral wool pipe section insulationPrimary

CAWS

U90/490 Site-applied insulation to ductwork

U90/490 Site-applied insulation to ductwork

Specification data - Mineral wool pipe section insulation

Standard

To EN 14303.

Recycled content

Up to 82%.

Thermal conductivity

0.032–0.054 W/m·K (10–120°C).

Guidance for specification option:

  • 0.032 W/m·K at 10°C.
  • 0.037 W/m·K at 40°C.
  • 0.039 W/m·K at 50°C.
  • 0.049 W/m·K at 100°C.
  • 0.054 W/m·K at 120°C.

Fire performance

To EN 13501-1, Euroclass Reaction to Fire: Class A2, s1, d0.

Insulation thickness (minimum)

25 mm.

40 mm.

50 mm.

Vapour barrier

-

Material

Aluminium foil.

Execution

Installing foil faced mineral wool insulation on ductwork.

Product Reference

ISOVER CLIMCOVER Roll Alu2

Service temperature

5–150°C.

Manufacturer guidance

Suitable for continuous service temperatures from 5°C to 150°C. The temperature on the aluminium facing should not exceed 80°C. For applications over 150°C, contact manufacturer's technical support centre. When using the product for the insulation of ductwork with a surface temperature below dew point, care must be taken to ensure a 100% vapour barrier is maintained.

Compliance with Building Regulations Part H

-

Manufacturer guidance

Compliance with the following:

  • England, Wales and Scotland: BS 5422: 2009 or TIMSA Guidance for Achieving Compliance with Part L of the Building regulations.
  • For Scotland, also refer to Technical Handbooks; Domestic Handbook 2010 and Non-Domestic Handbook 2010 Sections 6 – Energy.

Handling

Manufacturer’s standard.

Manufacturer guidance

Information regarding storage, installation and handling of ISOVER products, or health and safety information, can be found on the manufacturer's website.

Third party product certification

ISO 14001; ISO 9001.

Guidance for specification option:

Environmental:

  • Manufactured under Environmental Management System - ISO 14001.
  • Zero Ozone Depletion Potential (ODP) and Global Warming Potential (GWP) <5.
  • The manufacturing process does not use or contain CFCs, HCFCs or other damaging gases.


Quality:

  • Manufactured under Quality Management System - ISO 9001.

Sustainability data

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

82 %

Manufacturer guidance

CLIMCOVER Roll Alu2 is manufactured from up to 82% recycled glass