Verified by manufacturer 2 days ago
High Ingress Protection - IP65
Honeywell Morley-IAS wall mount sounder strobe is a high quality loop powered device designed to alert building occupants of an emergency.
Intelligent wall mount sounder strobe that is suitable for use in the following applications:
Intelligent wall mount sounder strobe that utilizes the Morley-IAS B501AP base for improved installation flexibility. When triggered by the fire panel its powerful sounder and intense strobe give a visible and audible warning. A choice of output levels and tones make the device suitable for a wide variety of applications. The Wall Mount sounder strobe integrates a 32 tone sounder and high quality strobe into one device. It is powered by the fire panel via the loop wiring. Control of the device is enabled using on-board switches, some of which can also be adjusted through SS Advanced Protocol. The device is installed simply by a twist fit onto the B501AP base.
Features and benefits:
Color | White Red Orange Clear |
Finish | Smooth |
Material | Plastic |
Shape | Circle |
Length | 121 mm |
Width | 121 mm |
Height | 64 mm |
Uniclass | |
CAWS | W90/337 Sounders S92/420 Alarm devices |
Classification data | |
Standard | To BS EN 54-23. |
Third-party certification | LPCB-approved. |
Rated voltage | 24 V d.c. |
Enclosure protection | To BS EN 54-3, Type A. |
Sound pressure level (minimum) | 97 dBA at 1 m. Guidance for specification option:
|
Integral beacon | To BS EN 54-23. |
Mounting | High IP. |
Power supply | From loop. |
Voltage | 15–29 V d.c. |
Current | 120 μA (non-isolation) 225 μA (isolation). Manufacturer guidanceStandby current - maximum. |
Operating temperature | -10°C to +55°C. |
Humidity | 93% ±3% non condensing. |
Ingress protection | IP65. |
Body colour | Pure white. Red. |
Lens | Clear. Guidance for specification option: Approved to EN 54-23 as an open class device. Coverage details are available on the installation manual. Red. Guidance for specification option: Not approved to EN 54-23 (Visual Alarm Devices) and must not be used as a visual alarm device or to provide a primary warning notification of fire. Amber. Guidance for specification option: Not approved to EN 54-23 (Visual Alarm Devices) and must not be used as a visual alarm device or to provide a primary warning notification of fire. |
Isolator | Isolation. Non-isolation. |
Base | WRR - high IP surface mount deep base in red. WPW - high IP surface mount deep base in red. |
Material | Plastic |