NBS Source
I'm a manufacturer
Compare variants

GenieEvo - Air Insulated MV Switchgear 3.3–13.8 kV

Verified by manufacturer 5 months ago

Incomer/ feeder (VC)

Schneider Electric Ltd Variant:

GenieEvo offers six switchgear options and 18 protection and control module options, providing a total of 69 standard panel combinations.

Jump to:
+44 (0)870 608 8608 Website

Application

Energy:

  • Distribution substation; Delivery substation,

Industry:

  • Food and beverage; life sciences; automotive; oil and gas; metallurgy.

Cloud and service providers:

  • Data centres/ colocation services; Telecom service providers; web-based service providers; IT equipment and professional services.

Infrastructures:

  • Marine and shore power; airports; ports; water treatment;

Buildings:

  • Large commercial centres; hospitals; finance; hotels; education.

Description

GenieEvo offers six switchgear options and 18 protection and control module options, providing a total of 69 standard panel combinations.

69 pre-engineered standard panel combinations.

Customized solutions are also available on request.


GenieEvo comprises:

  • Cast resin encapsulated MV system;
  • Demountable vacuum circuit breaker;
  • Controlled air, resin encapsulated series disconnector;
  • Flexible pre-engineered protection and control modules;
  • Smart grid and asset management ready.


Features and benefits:

  • Fixed pattern, offering the following customer benefits:
  • Reduced substation dimensions;
  • Saving civil and land costs;
  • No racking mechanism;
  • Fewer switchgear components;
  • Easier to operate;
  • No associated maintenance;
  • No withdrawable isolation contacts;
  • No associated maintenance;
  • Fully encapsulated MV system.
  • Pre-engineered, offering the following customer benefits:
  • Reduced lead time;
  • Reduced engineering at factory;
  • Production line optimized for standard panels;
  • Reduced engineering time for client;
  • Lower selling costs;
  • Reduced labour time during manufacture;
  • Reduced contract engineering time;
  • Manufacturing unit optimized for standard panels;
  • Less technical onus on client;
  • Application based solutions;
  • All information available pre-order;
  • Schemes designed as a package solution.

General information

Color

White

Material

Metal

Guidance for specification option:

Housing.

Other

Shape

Rectangle

Length

1230 mm

Guidance for specification option:

Depth.

Width

500 mm

750 mm

Height

2108 mm

Uniclass

Pr_60_70_36_53 High-voltage modular switchboardsPrimary

Specification data - High-voltage modular switchboards

Standards

To IEC 62271-1, IEC 62271-100, IEC 62271-103, IEC 62271-200 and IEC 62271-102.

Guidance for specification option:

Also:

  • IEC 61869; IEC 60255; BS 5311; ENA TS 50-18.

Third-party certification

All units are internal arc tested to EN ATS 41-40/IEC 62271-200.

Format

Metal-enclosed.

Internal arc classification

IAC-AF 25 kA 1s when tested to IEC 62271-200.

Rated voltage (Ur)

13.8 kV.

Rated frequency

50 Hz.

60 Hz.

Rated insulation levels

-

Rated lightning impulse withstand voltage (Up)

95 kV phase-to-phase, phase-to-earth.

Rated short-time withstand current (Ik)

25 kA for three seconds.

Partition class

LSC2A-PM.

Current rating

200 A.

Guidance for specification option:

Dimensions (height x depth x width): 2108 x 1230 x 500 mm.

630 A.

Guidance for specification option:

Dimensions (height x depth x width): 2108 x 1230 x 500 mm.

1250 A.

Guidance for specification option:

Dimensions (height x depth x width): 2108 x 1230 x 500 mm.

2000 A.

Guidance for specification option:

Dimensions (height x depth x width): 2108 x 1230 x 750 mm.

2500 A.

Guidance for specification option:

Dimensions (height x depth x width): 2108 x 1230 x 750 mm.

Fan cooled when current exceeds 2100 A; consult manufacturer for details.

Transformers

Guidance for specification option:

Consult manufacturer's literature for current (CT) and voltage (VT) transformers and insert requirements.


Current transformers:

Ring type, air insulated current transformers are used for protection, indication and metering. Standard CT specification (ratio, class, and burden) have been selected to suit the network requirements.

If the standard current transformers do not suit your specific application consult the manufacturer.


Voltage transformers:

Cast resin voltage transformers are used for protection, indication and metering. Standard VT specification (system voltage, class, and burden) have been selected to suit the network requirements. However, if the standard voltage transformers do not suit your specific application consult the manufacturer.

  • Fused VTs for circuit breakers.
  • Fused VTs for right hand busbar only.
  • Fused VTs for busbar metering.

Integral accessories

P1 General purpose feeder or incomer.

P2 Transformer feeder.

P3 Cable feeder with advanced monitoring and control.

P4 Unit protected cable feeder.

P5 Unit protected cable feeder with back up overcurrent and measurement.

Show more

Options

Guidance for specification option:

Consult manufacturer's literature for options and insert requirements for transducers, electrical trip/ close etc.

Accessories

Gland plate.

Guidance for specification option:

Consult manufacturer for gland plate options and insert requirements.

Main cable box entry.

Guidance for specification option:

Bottom or top entry; options will vary depending on model specified - consult manufacturer for options and insert requirements.

None.

Key interlocks.

Phase comparitors.

Designation

Guidance for specification option:

The designation of the type tested GenieEvo switchgear gives information about its design and rated electrical parameters.


Determined by options selected:

  • Product name (GenieEvo);
  • Network function (variant code);
  • Current rating code;
  • Transformer feeder protection and control module code.


Insert details based on specification data.

Sustainability data

Material

Metal

Guidance for specification option:

Housing.

Other