High-density, sustainable, easy-to-deploy power protection for large and hyperscale data centres.
For large and hyperscale data centres.
The Galaxy family of UPSs delivers highly efficient, simple-to-deploy, compact 3-phase UPS power protection. With innovative eConversion mode, Li-ion options and a range of 10 kW to 1500 kW, the Galaxy UPS seamlessly integrates into the electrical, physical and monitoring environment of customers operating data centres, industrial applications or facilities.
Features and benefits:
Color | White |
Finish | Powder-coated |
Material | Metal |
Shape | Rectangle |
Length | 1000 mm |
Width | 1200 mm |
Height | 1970 mm |
Warranty description | One year Guidance for specification option: One year on-site repair or replace with factory authorized start-up. |
Uniclass | |
CAWS | W53/380 Power supply units W53/380 Power supply units |
Description | Highly efficient, compact, modular uninterruptible power supply (UPS). |
Manufacturer | Schneider Electric Ltd. |
Standards | To BS EN IEC 62040-1 and BS EN IEC 62040-3. |
Mode of operation | Online Double Conversion. Eco-Mode. ECONversion. |
Configuration | Unitary. Parallel. Parallel Redundant. Synchronised. |
Efficiency | |
Overall (minimum) | Double conversion mode: up to 97.5%. eConversion mode: up to 99%. |
Eco mode (minimum) | Up to 99%. |
Input | |
Nominal voltage | Three-phase 380 V. Three-phase 400 V. Three-phase 415 V. |
Voltage tolerance | +/-15%. |
Frequency | 40–70 Hz. |
Power factor | >0.99 at load >25%. |
Total harmonic distortion (THD) | <3% at full linear load (symmetrical). |
Inverter output | |
Rated output apparent power | 500 kVA. 625 kVA. 750 kVA. 875 kVA. 1000 kVA. 1125 kVA. 1250 kVA. Manufacturer guidanceNominal power rating (kVA = kW). |
Nominal voltage | Three-phase 380 V. Three-phase 400 V. Three-phase 415 V. |
Voltage tolerance | +/-1% (symmetrical load). +/-3% (asymmetrical load). |
Total harmonic distortion (THD) | <1% with linear load. <5% with non-linear load. |
Nominal frequency | 50/60 Hz. |
Frequency tolerance | +/-0.1% free running. |
Overload capability | ≤125% for 10 minutes. ≤150% for 1 minute. Guidance for specification option:
Manufacturer guidanceOverload normal operation. |
Output power factor (minimum) | 1 at 40°C. Guidance for specification option: Power factor = 1 at 40°C (104°F) without derating 0.5 leading to 0.5 lagging without derating. |
Crest factor | 3. |
Maintenance bypass | External. |
Batteries | |
Location | External to UPS. |
Type | Valve-regulated lead-acid (VRLA). Lithium-ion. |
Voltage | 480–576 V. |
Number of cells (minimum) | 40–48 blocks. |
Battery supply d.c. circuit breaker with overload and short circuit protection | Required. |
Controls, indicators and alarms | |
LCD display | 10-inch colour touch display. |
Audible alarms | |
Type | Integral alarm within UPS enclosure. |
Enclosure | |
Ingress protection (minimum) | IP20. |
Material and construction | |
Type | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Finish | Epoxy powder-coated. |
Colour | White (RAL 9003). |
Lockable access doors | Required. |
Cable entry with removable gland plates | For top entry cables. |
Noise emission | |
Sound pressure level in normal mode (maximum) | <78 dBA at 100% load. Guidance for specification option: <69 dBA at 70% load. |
Sound pressure level in battery mode (maximum) | Manufacturer guidanceConsult manufacturer for details and insert requirement. |
Operating temperature | 0 to 40 °C without derating. |
Minimum storage temperature | -25 to 55 °C. |
Humidity | Operating: 5 to 90%, noncondensing. |
Dimensions | 1200 x 1000 x 1970 mm. Manufacturer guidanceWidth x depth x height. |
Accessories | Not required. Lithium-ion battery cabinet. Empty VRLA battery cabinet. Battery breaker box. Battery breaker kit. Manufacturer guidanceConsult manufacturer for details. |
Material | Metal |
Recyclability | 61% recyclability potential at end of life |
Expected Life | 15 year |