Verified by manufacturer 6 months ago
DN15
UK Conformity Assessed (UKCA)
Certificate type
Statement of compliance
Certificate type
Threaded Low Flow PICV Range with Equal Percentage Control Characteristic.
Heating or cooling, fan coil units, variable air volume system, cooling ceilings and other terminal units - wherever dynamic balancing and fully accurate temperature control are required.
Two way modulating Pressure Independent Control Valve with easily removable insert. Widely used in UK in FCU installations in well insulated buildings that typically require low flow rates and valves that accurately control these low flow rates.
The GreEQ Low Flow PICV offers flow rates from 0.0048 L/s, with small steps between the set points and 11 set points under 0.02 L/s, delivering a fully controlled indoor climate and optimised energy use.
Features and benefits:
Color | Gold |
Finish | Brass |
Material | Brass |
Shape | Other |
Length | 82 mm |
Width | 36.7 mm |
Height | 143 mm |
Warranty description | 18 months |
Uniclass |
Product range |
Pressure rating | 25 Bar. |
Temperature range | -20°C/120°C. |
Material | Brass. |
Actuator | FN.Guidance for specification option: Electrical actuators 0(2) - 10 V modulating, 3 point floating or 2-position FNR.Guidance for specification option: Electrical actuators 0-10 V modulating, 3 point floating or 2-position. FT.Guidance for specification option: Thermal actuators 0-10 V modulating or ON/OFF. Manufacturer guidanceConsult literature for details and insert requirements. |
Accessories | GreEQ.0 0.00482 – 0.126 l/s.GreEQ.1 0.00764 – 0.224 l/s.FlowCon Insulation Shell.Guidance for specification option: Polypropylene foam shell. Class F to EN 13501. Consult literature for details and insert requirements. |
Type: | GEQ.1.33.03.B.F.F.I. Guidance for specification option: Consult literature for product code and selections. |
Valve size | 1/2". Guidance for specification option:
|
Country of material origin | Denmark |
Country of product manufacture | Denmark |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 11.0 kg CO₂ eq/unit Self declared |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 70 % |
Platform | Compatible | Version |
---|---|---|
- | 1 |
UK Conformity Assessed (UKCA)
FlowCon FN/FH Actuator Range UKCA Certificate
UK Conformity Assessed (UKCA)
FlowCon FNP Actuator UKCA Certificate
Statement of compliance
FlowCon GreEQ PICV PED Certificate
Statement of compliance
FlowCon Registration, Evaluation, Authorisation and Restriction of Chemicals [REACH]
Statement of compliance
FlowCon Restriction of Hazardous Substances [RoHS]
Statement of compliance
FlowCon Waste from Electrical and Electronic Equipment Statement [WEEE]