Fire-resistant roller shutters tested to European standards EN 1634-1 offering up to 240 minutes integrity performance (E240) for various substrates (Masonry, Timber Stud Partition, Steel).

Jump to:
Request BIM
+44 (0)1204 853243 Website

Application

Suitable for installation in masonry, concrete, timber stud partitions, and protected structural steel supporting constructions. Designed for use as fire-resistant roller shutters in door applications providing fire integrity performance up to 240 minutes depending on the model and installation type.

Description

As the manufacturer and trade supplier of the Flame Armour™ product range, the fire-resistant roller shutters are tested in accordance with the latest European standards, ensuring full compliance with current industry guidance and government requirements. Flame Armour™ fire shutters has been assessed on both rigid and flexible supporting constructions, achieving an integrity performance of up to 240 minutes.

Features and benefits:

  • Designed, tested and certified for installation to Finished Floor Level (FFL).
  • Approved for masonry, concrete, timber stud partition and protected structural steel supporting constructions.
  • Integrity performance of up to 240 minutes (E60 / E90 / E120 / E240).
  • CE and UKCA marked for full compliance with Building Regulations.
  • Furnace tested to EN 1634-1:2014 + A1:2018 (superseding BS 476: Part 22: 1987).
  • Gravity fail-safe motor option closes automatically in case of fire or power failure.
  • Suitable for ‘Rigid’ and ‘Flexible’ supporting constructions as defined within EN 1363-1.
  • Offering both tubular and inline (chain-driven) industrial motor applications.

Suitable applications:

  • Commercial kitchens and catering facilities
  • Restaurants, cafés, and food courts
  • Hospitals and healthcare facilities
  • Care homes and assisted-living facilities
  • Hotels and hospitality venues
  • Retail units and shopping centres
  • Supermarkets and food preparation areas
  • Transport hubs (airports, railway stations, service areas)
  • Staff and public canteens
  • Office buildings and business premises
  • Industrial premises and industrial units
  • Warehouses and logistics centres
  • Factories and manufacturing facilities
  • Chemical plants and high-risk industrial environments
  • Power generation facilities, including nuclear power stations
  • Educational buildings, including schools and universities
  • Airports

General information

Color

Grey

Other

Guidance for specification option:

This product is supplied galvanized as standard, at additional costs it is possible to powder coat the full roller shutter assembly any RAL or BS colour.

Finish

Galvanized

Guidance for specification option:

As standard.

Powder-coated

Guidance for specification option:

Optional.

Material

Steel

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Uniclass

Pr_30_59_84_30 Fire-resisting roller shuttersPrimary

CAWS

L20/60 Doors

L20/610 Roller shutters/ curtains

Specification data - Fire-resisting roller shutters

Classification data

Standard

UKCA/ CE marked to BS EN 16034.

Opening sizes

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Format

Internal.

Arrangement

Vertical, face-fitted across opening.

Performance

-

Fire performance

-

Fire resistance

To EN 13501-1, E60.
To EN 13501-1, E90.
To EN 13501-1, E120.
To EN 13501-1, E240.

Frame and guides

-

Material

-

Finish

Galvanized.
Powder-coated.

Colour

Grey.

Guidance for specification option:

Galvanized as standard.

RAL colour.

Guidance for specification option:

Insert requirements.

BS colour.

Guidance for specification option:

Insert requirements.

Manufacturer guidance

This product is supplied galvanized as standard, at additional costs it is possible to powder coat the full roller shutter assembly any RAL or BS colour.

Film thickness (minimum)

Coating applicator to determine.

Installation fasteners

Manufacturer's standard.

Frame accessories

End plates.

Manufacturer guidance

Depending on the dimensions of the structural height and the specification stated within the Extended Application Report, this component sizes will vary (250 mm to 500 mm).

Shutter curtain

-

Lath material

Galvanized steel.

Profile

Curved.

Manufacturer guidance

Constructed from 75 mm wide curved interlocking galvanized steel 0.7 mm or 0.9 mm solid, complete with cast end locks.

Finish and colour

Galvanized.

Guidance for specification option:

Galvanized as standard.

Powder-coated, RAL colour.

Guidance for specification option:

Insert requirements.

Powder-coated, BS colour.

Guidance for specification option:

Insert requirements.

Accessories

Not required.
UPS-FDI control panel.
FCP Lite audio-visual panel.
UPS Sleep-mode battery backup.
FDCP01 Control panel.
FDCP01 Repeater panel.
FCP03 Audio-visual panel.
FPC03 Repeater panel.
(CSL) Sleep mode UPS and fire alarm interface card.
Standard battery backup.
Red emergency and green 'door release' buttons.
Green 'emergency open' button.
Red 'mushroom' button.
Fixed temperature thermal detector (heat detector).
Lockable 'test' and 'reset' push button station.

Manufacturer guidance

Depending on the type of fire-resistant roller shutter required, the following components are either a requirement or an additional extra. Consult manufacturer and insert requirements.

Sustainability data

Contains Red List materials

No

Country of product manufacture

United Kingdom

Material

Steel

Product certifications

Warringtonfire

Warringtonfire

CE Certificate Of Constancy Of Performance (AVCP) - FLAME ARMOUR (DOORSET) Fire-Resistant Roller Shutter E60 / E90 / E120/ E240

Warringtonfire

Warringtonfire

UKCA Certificate Of Constancy Of Performance (AVCP) - FLAME ARMOUR (DOORSET) Fire-Resistant Roller Shutters E60 / E90 / E120 / E240

Warringtonfire

Warringtonfire

FLAME ARMOUR (DOORSET) - Classification Report No. 416674

Similar products from SSS Industrial Doors Ltd

FLAME ARMOUR+ (Servery Hatch) Fire-Resistant Roller Shutters - Fire-resistant roller shutters

FLAME ARMOUR+ (Servery Hatch) Fire-Resistant Roller Shutters - Fire-resistant roller shutters