NBS Source
I'm a manufacturer

Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina

Verified by manufacturer 1 month ago

Coopers Fire Ltd Third party certifications:
  • IFCC

    IFCC

    Certificate type

Fire curtain developed to provide high performance fire protection through tests to British and Underwriters Laboratories (UL) standards.

Jump to:
BOS
+44 (0)23 9245 4405 Website

Application

Suitable to be used to form a virtually continuous barrier as a fire separating element and for use in atriums, boundary protection, compartmentation, stairs and escalators.

Description

An electrically operated active fire curtain barrier assembly. Barrier assemblies comprise a metallic fabric, fan-folded and retained in a metal tray, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A special bottom tray is fitted to the bottom of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.


The edges of the fire curtain are retained inside side guides, providing pressure resistance of 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position. Barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s). Barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Fire Resistance’ (120 minutes' integrity). Barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 for ‘Radiant Heat Flux’ (30 minutes).


The fabric used in the barrier assemblies have been tested to BS 476-6 and BS 476-7.


Operation:

Fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery backup power. At the end of the period, the barrier assembly will deploy.


Fire resistance:

240 minutes (four hours) integrity.


Radiation resistance:

120 minutes <15 kW/m².


Classification:

E180 EW30.


Product certification, performance and/ or testing:

  • Barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Barrier assemblies have been tested for fire resistance to BS EN 1634-1, as required by BS 8524-1. The barrier assembly achieved 240 minutes integrity and 30 minutes radiation.
  • Barrier assemblies have been tested for reliability, durability and self-closing to BS EN 14600 as required by BS 8524-1.
  • Barrier assemblies have been tested for gravity fail-safe as required by BS 8524-1.
  • Motor(s) used in barrier assemblies in the above tests have been tested for operation at temperatures of 400°C as required by BS 8524-1.
  • The fabric used in the barrier assemblies have been tested to BS EN ISO 1716.
  • The fabric used in the barrier assemblies have been tested to BS 476 pt 6 and pt 7.
  • The fabric used in the barrier assemblies have been tested to BS EN 13823.
  • The fabric used in the barrier assemblies have been tested to BS 6853.
  • The fabric used in the barrier assemblies have been classified as 'A1' to EN 13501-1.


Approving standards:

The following standards apply to this product:

  • BS 8524-1:2013, Specification for active fire curtain barrier assemblies.
  • BS EN 1634-1:2014, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows.
  • BS EN 1363-1:2012, Fire resistance tests – Part 1: General requirements.
  • BS EN 1363-2:1999, Fire resistance tests – Part 2: Alternative and additional procedures.
  • BS EN 13501-2:2007+A1, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating.
  • BS EN 14600:2005, Doorsets and openable windows with fire resisting and/ or smoke control characteristics. Requirements and classification.
  • BS EN ISO 1716:2010, Reaction to fire tests for products. Determination of the gross heat of combustion (Calorific value).
  • BS 476-6, Method of test for fire propagation for products.
  • BS 476-7, Method of test to determine the classification of the surface spread of flame for products.
  • BS 6853: 1999 – Annex D.8.4, Methods for measuring smoke density.
  • BS EN 13823, Reaction to Fire Tests – Single Burning Item.
  • BS EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements. Classification using test data from reaction to fire tests.
  • BS EN ISO 14184-1:2011. Textiles. Determination of formaldehyde. Free and hydrolysed formaldehyde (water extraction method).
  • BS EN ISO 9001:2015, Quality management system.
  • BS EN ISO 14001:2015, Environmental management system.

General information

Color

Silver

Other

Grey

White

Finish

Galvanized

Powder-coated

Material

Fabric

Guidance for specification option:

Metallic fabric.

Shape

Circle

Oval

Square

Triangle

Rectangle

Show more

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

To BS 8524-1, BS EN 1634-1, BS 5234-2, BS EN 14600, BS EN 13501-2, BS EN ISO 1716, BS EN 13501-1+A1, BS EN ISO 14184-1, BS EN 12101-10. Compliant to PAS 121:2007 (where applicable).

Barrier assemblies

To BS 8524-1.

Test standards

To BS 8524-1, BS EN 1634-1 and UL 10D.

Third-party certification

IFCC Intertek UL.

Size

400 x 500 x 210 mm and 300 x 200 x 80 mm.

Guidance for specification option:

Insert requirement, available in unlimited widths and drops up to 8.0 m. Power supply size (w x h x d) and motor control unit size (w x h x d).

Performance

-

Pressure and impact

SD.

Durability class

C1.

Smoke containment

None.

Fire resistance

Fire resistance:240 minutes (four hours) integrity.

Reaction to fire

To BS EN 13501-2, A1.

Guidance for specification option:

Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating.

Barrier units

Single.

Multiple.

Manufacturer guidance

Flexible metallic fabric.

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m² -5% +10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance).
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item).
  • The fabric has passed testing to BS 6853 (Methods for measuring smoke density).
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).

Deployment

Full.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Split drop delay.

Guidance for specification option:

To partially deploy to pre-determined level to permit escape, and initial smoke containment. After delay fully deploys to its fire operational position when mains, or emergency power is available.

Visual alert system.

Guidance for specification option:

Light warning system when mains or emergency power is available.

Voice warning.

Guidance for specification option:

Audio or spoken multi message facility when mains or emergency power is available.

Classification

E180 EW30.

Frame colour/ finish

Polyester powder-coated.

Guidance for specification option:

Insert requirement.

Galvanized.

Concealment

Flush fit.

Suspended ceiling with recessed shallow gap.

Suspended ceiling with patented SLAT™.

Guidance for specification option:

Self levelling access trim.

Type

Not required.

Face fixed.

Recessed fixed.

Orientation

Not applicable.

Vertical.

Finish

Not applicable.

Galvanized steel.

Powder coated.

Guidance for specification option:

Available upon request, insert colour requirements.

Zintec

Painted

Fixing

I beam.

Soffit.

Suspended with unistrut fit.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

285.92 kg CO₂ eq/kg

Self declared

Guidance for specification option:

285.92 tCO2e for yearly emissions.

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit

Revit 2017

2

IFC
-

2

Third party certifications

IFCC

IFCC

IFC Certification

Literature

FireMaster® Concertina™  Active Fire Curtain Barrier

FireMaster® Concertina™ Active Fire Curtain Barrier

Examples of FireMaster and SmokeStop Concertina Installations

Examples of FireMaster and SmokeStop Concertina Installations

Case studies

Aldgate Tower, London Multisided Concertina Fire Curtains

Aldgate Tower, London Multisided Concertina Fire Curtains

Five Guys Restaurant, Dubai Marina Mall. FireMaster Concertina multi-side fire curtain

Five Guys Restaurant, Dubai Marina Mall. FireMaster Concertina multi-side fire curtain

Leabaib Health Centre, Doha, Qatar - FireMaster Concertina and FireMaster Fire Curtains

Leabaib Health Centre, Doha, Qatar - FireMaster Concertina and FireMaster Fire Curtains

Nova, Victoria, UK - FireMaster Concertina Fire Curtains

Nova, Victoria, UK - FireMaster Concertina Fire Curtains

One Creechurch Place, London - FireMaster Concertina Fire Curtains

One Creechurch Place, London - FireMaster Concertina Fire Curtains

Similar products from Coopers Fire Ltd

Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain.  - Fire Curtain Vision Panel

Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel

Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain

Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina

Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers

Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain

Fire Curtain Vii® Fire A1 - Vertical Active Fire Curtain - Vertical Fire Curtain