NBS Source
I'm a manufacturer

FireMaster® Concertina™ Egress Fire Curtain

Verified by manufacturer 7 months ago

Coopers Fire Ltd Third party certifications:
  • KIWA BDA

    KIWA BDA

    Certificate type

  • Constructionline Gold

    Constructionline Gold

    Certificate type

Concertina fire curtain with integral egress door allowing for safe evacuation. Tested and Certified to BS EN 1634-1 for 90 minutes.

Jump to:
+44 (0)23 9245 4405 Website

Application

Suitable for use in atria, boundary protection, compartmentation, stairs and escalators.

Description

An electrically operated FireMaster® Concertina™ A1 Egress active fire curtain barrier assembly used to form a virtually continuous barrier as a fire separating element.


The system comprise a stainless-steel reinforced glass fibre fabric, fan-folded and retained in a metal tray, powered by an internal 24 V dc electric motor, enclosed within a 1.2 mm-thick stainless steel box. Within the main curtain assembly there is an egress door allowing for evacuation of personnel and for access for fire services. The egress door may contain up to two vision panels, allowing first responders visual access to the fire side of the curtain.


A bottom tray is attached to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.


The 24V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.


The fire curtain assembly has been tested to the requirements of BS EN 16034:2014 for ‘Durability of Self-Closing against degradation’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s).


The assemblies have been tested to the requirements of BS EN 1363-1: for ‘Fire Resistance’ (90 minutes) and for ‘Radiation’ (60 minutes).


Operation:

FireMaster® Concertina™ A1 Egress active fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function.


Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. During this period, the Barrier assembly will deploy on receipt of a signal. At the end of the period, the Barrier assembly will deploy.


Fire resistance:

90 minutes integrity.


Radiation resistance:

60 minutes <15 kW/m².


Product certification, performance and/ or testing:

  • Barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Barrier assemblies have been tested for fire resistance to BS EN 1634-1, as required by BS 8524-1. The barrier assembly achieved 90 minutes integrity and 60 minutes radiation.
  • Complete FireMaster® Concertina™ A1 Egress active fire curtain barrier assemblies have passed tests for durability to BS EN 12605 (500 cycles), and for self-closing to BS EN 16034 (C1).
  • Motor(s) used within FireMaster® A1 Egress active fire curtain barrier assemblies have been cycle tested for 50,000 operations (C3).
  • Motor(s) used within FireMaster® Concertina™ A1 Egress active fire curtain barrier assemblies have passed elevated temperature operational tests to BS 8524-1:2013, Annex G.


Approving standards:

The following standards apply to this product:

  • BS EN 1634-1:2014+A1:2018: Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows
  • BS EN 1363-1:2020: Fire resistance tests – Part 1: General requirements.
  • BS EN 1363-2:1999: Fire resistance tests – Part 2: Alternative and additional procedures.
  • BS EN 12605:2000: Industrial, commercial and garage doors and gates. Mechanical aspects. Test methods.
  • BS EN 16034:2014: Pedestrian doorsets, industrial, commercial, garage doors and openable windows - Product standard, performance characteristics - Fire resisting and/or smoke control characteristics.
  • BS 476-6:1989+A1:2009: Fire tests on building materials and structures. Method of test for fire propagation for products.
  • BS 476-7:1997:, Fire tests on building materials and structures. Method of test to determine the classification of the surface spread of flame of products.
  • BS EN ISO 1716: Determination of the Heat of Combustion for Building Products.
  • BS 6853 Annex B.2: Toxicity.
  • BS 6853 Annex D.8.4: Methods for Measuring Smoke Density.
  • BS EN 14184-1: Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).
  • BS EN ISO 9001:2008: Quality management system.
  • BS EN ISO 14001:2004: Environmental management system.
  • BS EN ISO 45001:2018: Occupational Health and Safety Management

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Fabric

Guidance for specification option:

Metallic fabric.

Shape

Rectangle

Circle

Square

Other

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_94 Vertical active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Vertical active fire curtain barriers

Standards

BS EN 1634-1, BS EN 1363-1, BS EN 1363-2, BS EN 12605, BS EN 16034, BS 476-6, BS 476-7, BS EN ISO 1716, BS 6853, BS 6853, BS EN 14184-1.

Size

Guidance for specification option:

Insert requirements.

Performance

-

Fire resistance

90 minutes integrity.

Barrier units

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m² -5%, + 10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS 476-6 (Method of test for fire propagation for products).
  • The fabric has passed testing to BS 476-7 (Method of test to determine the classification of the surface spread of flame for products).
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item)
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).
  • The fabric has a Classification of Reaction to Fire Perfromance in accordance with EN 13501-1:2007 +A1:2009 of ‘A1’.

Deployment

Full.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Split drop delay.

Guidance for specification option:

To partially deploy to pre-determined level to permit escape, and initial smoke containment. After delay fully deploys to its fire operational position when mains, or emergency power is available.

Visual alert system.

Guidance for specification option:

Light warning system when mains or emergency power is available.

Voice warning.

Guidance for specification option:

Audio or spoken multi message facility when mains or emergency power is available.

ResQ Window.

Frame colour/ finish

Guidance for specification option:

Insert requirement.

Concealment

Flush fit.

Suspended ceiling with recessed shallow gap.

Suspended ceiling with patented SLAT™.

Guidance for specification option:

Self levelling access trim.

Fixing

I beam.

Soffit.

Suspended with unistrut fit.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

KIWA BDA

KIWA BDA

CERTIFICATED INSTALLER OF ACTIVE FIRE PROTECTION

Constructionline Gold

Constructionline Gold

CERTIFICATE OF MEMBERSHIP

Literature

Firemaster Concertina Egress Fire Curtain brochure

Firemaster Concertina Egress Fire Curtain brochure

Examples of FireMaster and SmokeStop Concertina Installations

Examples of FireMaster and SmokeStop Concertina Installations

Similar products from Coopers Fire Ltd

FireMaster® 4/1000 - Vertical Active Fire Curtain

FireMaster® 4/1000 - Vertical Active Fire Curtain

FireMaster® A1 - Active Fire Curtain

FireMaster® A1 - Active Fire Curtain

FireMaster® A1 ResQ-Window

FireMaster® A1 ResQ-Window

FireMaster® Cleanroom - Vertical Active Fire Curtain

FireMaster® Cleanroom - Vertical Active Fire Curtain

FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain

FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain

FireMaster® Concertina Open - L Shape - Concertina Fire Curtain

FireMaster® Concertina Open - L Shape - Concertina Fire Curtain

FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain

FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain

FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain

FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain

FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain

FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain

FireMaster® Plus² - Vertical Active Fire Curtain

FireMaster® Plus² - Vertical Active Fire Curtain