Verified by manufacturer 27 days ago
KIWA BDA
Certificate type
Constructionline Gold
Certificate type
Concertina fire curtain with integral egress door allowing for safe evacuation. Tested and Certified to BS EN 1634-1 for 90 minutes.
Suitable for use in atria, boundary protection, compartmentation, stairs and escalators.
An electrically operated FireMaster® Concertina™ A1 Egress active fire curtain barrier assembly used to form a virtually continuous barrier as a fire separating element.
The system comprise a stainless-steel reinforced glass fibre fabric, fan-folded and retained in a metal tray, powered by an internal 24 V dc electric motor, enclosed within a 1.2 mm-thick stainless steel box. Within the main curtain assembly there is an egress door allowing for evacuation of personnel and for access for fire services. The egress door may contain up to two vision panels, allowing first responders visual access to the fire side of the curtain.
A bottom tray is attached to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.
The 24V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.
The fire curtain assembly has been tested to the requirements of BS EN 16034:2014 for ‘Durability of Self-Closing against degradation’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.08 m/s).
The assemblies have been tested to the requirements of BS EN 1363-1: for ‘Fire Resistance’ (90 minutes) and for ‘Radiation’ (60 minutes).
Operation:
FireMaster® Concertina™ A1 Egress active fire curtain barrier assemblies commence movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function.
Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.
In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. During this period, the Barrier assembly will deploy on receipt of a signal. At the end of the period, the Barrier assembly will deploy.
Fire resistance:
90 minutes integrity.
Radiation resistance:
60 minutes <15 kW/m².
Product certification, performance and/ or testing:
Approving standards:
The following standards apply to this product:
Color | Other |
Finish | Galvanized Powder-coated |
Material | Fabric Guidance for specification option: Metallic fabric. |
Shape | Rectangle Circle Square Other |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year Guidance for specification option: From date of commissioning. |
Uniclass | |
CAWS | L20/610 Roller shutters/ curtains |
Standards | To BS EN 1634-1, BS EN 1363-1, BS EN 1363-2, BS EN 12605, BS EN 16034, BS 476-6, BS 476-7, BS EN ISO 1716, BS 6853, BS 6853, BS EN 14184-1. |
Barrier assemblies | To BS 8524-1. |
Test standards | To BS EN 1634-1, UL 10D, UL 864. |
Third-party certification | Certifi, UL. |
Size | Guidance for specification option: Insert requirements. |
Performance | |
Fire resistance | 90 minutes integrity. |
Barrier units | Flexible metallic fabric.Guidance for specification option:
|
Deployment | Full. |
Activation | Commences movement upon initiation of alarm or power or system failure. |
Accessories | None.Split drop delay.Guidance for specification option: To partially deploy to pre-determined level to permit escape, and initial smoke containment. After delay fully deploys to its fire operational position when mains, or emergency power is available. Visual alert system.Guidance for specification option: Light warning system when mains or emergency power is available. Voice warning.Guidance for specification option: Audio or spoken multi message facility when mains or emergency power is available. ResQ Window. |
Frame colour/ finish | Guidance for specification option: Insert requirement. |
Concealment | Flush fit. Suspended ceiling with recessed shallow gap. Suspended ceiling with patented SLAT™. Guidance for specification option: Self levelling access trim. |
Fixing | I beam. Soffit. Suspended with unistrut fit. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Material | Fabric Guidance for specification option: Metallic fabric. |
Recyclability | Coopers Fire offer a take back service where product is broken down into component parts. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
Platform | Compatible | Version |
---|---|---|
- | 1 |
Fire Curtain - FireMaster® A1 - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - FireMaster® A1 ResQ-Window for Fire Curtain. - Fire Curtain Vision Panel
Fire Curtain - FireMaster® Concertina Closed - Rectangular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina Open - L Shape - Concertina Fire Curtain - Fire Curtain Concertina
Fire Curtain - FireMaster® Concertina Open - Rectangular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Concertina™ Closed - Circular - Concertina Fire Curtain - Concertina Vertical Fire Curtain
Fire Curtain - FireMaster® Concertina™ Open - Circular - Concertina Fire Curtain - Fire Curtain Vertical Concertina
Fire Curtain - FireMaster® Plus² - Vertical Active Fire Curtain - Vertical Active Fire Curtain Barriers
Fire Curtain - Vii Fire i-Zone - Vertical Active Fire Curtain - Vertical Fire Curtain
Fire Curtain FireMaster® 4/1000 - Vertical Active Fire Curtain - Vertical Fire Curtain