Verified by manufacturer 4 days ago
24 V d.c. electric: actuator
Certificate of constancy of performance
Certificate type
The Firelight Duo provides natural smoke control and day-to-day ventilation with added daylight entry. Certified to EN 12101-2, it delivers high thermal, acoustic, and weather performance.
Suitable for natural smoke control and provision of extract ventilation for most kinds of industrial and commercial buildings.
The Firelight Duo is a dual-purpose natural ventilator providing both smoke control and day-to-day ventilation, while letting in natural light. Tested to EN 12101-2, it combines fully thermally broken construction with excellent acoustic insulation (up to 49 dB), high weather resistance (Class A9), and superior air tightness (Class 4). Available in sizes up to 2500 × 3000 mm with glass, polycarbonate, or aluminium infills, it offers flexible control options and a discreet low-profile design.
Product Highlights:
Product Technical Information
Dimensions:
Panel Options:
Thermal Performance (U value):
The Firelight Duo can achieve a U-Value of up to 1.01 W/m2 K depending on the variant selected. Please contact our technical team
Controls:
The Firelight Duo can be opened and closed either by double-acting pneumatic cylinders that lock in their ends positions, or by 24 V DC or 230 V AC electric actuators. A 230 V AC electric actuator offers the advantage over a 24 V DC electric actuator of a faster opening speed, as well as noticeably reduced wiring costs.
Certification + Test Results:
Acoustics:
Up to 49 dB.
Color | Silver Other |
Finish | Mill |
Material | Aluminium Polycarbonate Glass |
Shape | Rectangle Square |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/47 Roof ventilators L10/490 Roof ventilators |
Product range |
Classification data | |
Standard | To BS EN 12101-2. |
Opening type | B. |
Mounting | Roof mounted, onto curb. Roof mounted, onto glazing. Roof mounted, onto roof sheeting. |
Aerodynamic free area | Manufacturer's standard. Guidance for specification option: Consult manufacturer for maximum overall ventilator size. Determined by the selected type, the chosen controls, the ventilator’s application, its geometry and its installation angle. Manufacturer guidanceAerodynamic coefficient: up to 0.68. |
Reliability classification | Re 1000. Guidance for specification option: 10 000 cycles. |
Snow load classification | Up to 7000 N/m². |
Low ambient temperature classification | T (-15). |
Wind load classification | Up to 9000 N/m². |
Resistance to heat classification | B300-E. |
Arrangement | Twin flaps. |
Dimensions | |
Length | Manufacturer guidanceInsert requirements, 1000–3000 mm overall ventilator lengths in 1 mm increments. |
Width | Manufacturer guidanceInsert requirements; 1000–2500 mm overall ventilator widths in 1 mm increments. |
Height | Manufacturer's standard. |
Controls | 24 V d.c. electric: actuator. Pneumatic controls. Manufacturer guidanceBracket controls (for smaller vents and/or those installed into glazing) or control channel controls (for larger vents and/or heavier lids or need to keep actuator lengths short). |
Materials | |
Ventilator | |
Frame | Corrosion-resistant aluminium alloy. Guidance for specification option: Thermally broken. With stainless steel fixings. |
Glazing | Double glazed. Guidance for specification option: Insert requirements; 28, 30 or 32 mm overall thickness (maximum 50 mm) or customer specified (up to 60 kg/m²). Triple glazed. Guidance for specification option: Insert requirements; 28, 30 or 32 mm overall thickness (maximum 50 mm) or customer specified (up to 60 kg/m²). Polycarbonate, clear. Guidance for specification option: 16 or 25 mm overall thickness or customer specified (16–50 mm). Polycarbonate, opaque. Guidance for specification option: 16 or 25 mm overall thickness or customer specified (16–50 mm). Infill panel. Guidance for specification option: As standard a 2 mm-thick aluminium external sheet, 21 mm-thick infill with a mass of 30 kg/m² and heat transfer of 0.03 W/m·K, 2 mm-thick internal sheet. 25 mm overall thickness as standard, 16–50 mm possible. Noise reduction panel. (DUO RN) Guidance for specification option: Multi-layer system to achieve up to 49 dB Rw. Manufacturer guidance
|
Finish | Mill finish. Polyester powder-coated. Guidance for specification option: 70 µm thick as standard. Anodized. Guidance for specification option: 20 µm thick as standard. Other. Guidance for specification option: Special finishes available on request; consult manufacturer and insert requirements. |
Colour | Standard. Guidance for specification option: Mill finish/ anodized only. RAL. Guidance for specification option: Polyester powder-coated only; insert requirements. |
Integral upstands | |
Material | Corrosion-resistant aluminium alloy. |
Finish | To match frame. Mill finish. Polyester powder-coated. Guidance for specification option: 70 µm thick as standard. Anodized. Guidance for specification option: 20 µm thick as standard. Other. Guidance for specification option: Special finishes available on request; consult manufacturer and insert requirements. |
Colour | To match frame. Standard. Guidance for specification option: Mill finish/ anodized only. RAL. Guidance for specification option: Polyester powder-coated only; insert requirements. |
Seals | Manufacturer's standard. Guidance for specification option: Five high-grade, continuous EPDM and TPE seals, two of which seal the panels into the lids and three between the lids and the frame. As a result there is very low air leakage and a low U-value. |
Accessories | None. Wind baffles on two sides. Guidance for specification option: To improve aerodynamic performance. |
Locking | Double locking. |
Resistance to fire | E. Guidance for specification option: To EN 13501-1. |
U-value | Up to 0.5 W/m²K. Guidance for specification option: Values vary between 1.9 and 0.5 W/m²K. |
Air permeability | Class 4. Guidance for specification option: Tested in accordance with EN 12207: Air permeability. Value is dependent on the type of ventilator specified. |
Watertightness | Class 9A. Guidance for specification option: Tested in accordance with EN 12208: Water tightness. Value is dependent on the type of ventilator specified. |
Sound insulation | Up to 49 dB Rw. Guidance for specification option: Dependent on the type of ventilator specified. |
Material | Aluminium Polycarbonate Glass |