Fire Curtain - FireMaster® NVS™ Horizontal Duplex™ - Horizontal Active Fire Curtain - Horizontal Active Fire Curtain

Verified by manufacturer 5 months ago

Coopers Fire Ltd Third party certifications:
  • Warrington Fire

    Certificate type

Active fire curtain barrier assemblies that close from each end of a void to meet and shut in the middle.

Jump to:
BOS
+44 (0)23 9245 4405 Website

Application

Suitable for use in applications which require an active fire curtain barrier that close from each end of a void to meet and shut in the middle.

Description

The barrier assemblies comprise a fire-resistant fabric wound on to a steel roller, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick mild steel box. The edges of the curtain are retained inside side guides, providing pressure resistance of at least 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.


The barrier assemblies have been tested to the requirements of BS EN 14600:2005 for ‘Durability of Self-Closing’ (500 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.1 m/s). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 + A1:2018 for ‘Fire Resistance’ (120 minutes' integrity). The barrier assemblies have been tested to the requirements of BS EN 1634-1:2014 + A1:2018 for ‘Fire Resistance’ (120 minutes integrity).


Operation:

Barrier assemblies commence movement upon initiation of BMS alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.


Fire resistance:

120 minutes' (2 hours') integrity.


Radiation resistance:

15 minutes.


Product certification, performance and/ or testing:

  • Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/ IEC 17065:2012.
  • Complete barrier assemblies have been tested for fire resistance to BS EN 1634-1. The barrier assembly achieved 120 minutes integrity and 15 minutes radiation.
  • Complete barrier assemblies have passed tests for durability to BS EN 12605 (500 cycles).
  • Complete barrier assemblies have passed tests for durability to BS EN 12605 (500 cycles).


Approving standards:

The following standards apply to this product:

  • BS EN 1634-1:2014 +A1:2018, Fire resistance and smoke control tests for door, shutter and, openable window assemblies and elements of building hardware. Fire resistance tests for doors, shutters and openable windows.
  • BS EN 1363-1:1999, Fire resistance tests – Part 1: General requirements.
  • BS EN 13501-2:2003, Fire classification of construction products and building elements. Classification using data from fire resistance tests, excluding ventilation services rating.
  • BS EN 12605:2000, Industrial, commercial and garage doors and gates. Mechanical aspects. Test methods.
  • BS EN 14600, Doorsets and openable windows with fire resisting and/or smoke control characteristics – Requirements and classification.
  • BS 8524-1:2013, Annex G, “Test method for reliability of motor operation at elevated temperatures”.
  • BS 476 Pt 6, Fire tests on building materials and structures. Method of test for fire propagation for products.
  • BS 476 Pt 7, Fire tests on building materials and structures. Method of test to determine the classification of the surface spread of flame of products.
  • BS EN ISO 9001:2008, Quality management system.
  • BS EN ISO 14001:2004, Environmental management system.

General information

Color

Other

Finish

Galvanized

Powder-coated

Material

Fabric

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_38 Horizontal active fire curtain barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Horizontal active fire curtain barriers

Standards

-

Barrier assemblies

To BS EN 8524-1.

Test standards

Compliant to BS EN 1634-1:2014 +A1:2018.

Size

Guidance for specification option:

Insert requirement. Consult manufacturer for details.

Power supply size: 600 x 600 x 210 mm (w x h x d).

Performance

-

Pressure and impact

SD.

Durability class

C1.

Smoke containment

Not available.

Fire resistance

120 minutes (2 hours) integrity.

Barrier units

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m²-5%, +10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS 476-6 (Method of test for fire propagation for products).
  • The fabric has passed testing to BS 476-7 (Method of test to determine the classification of the surface spread of flame for products).
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance).
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item).
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).
  • The fabric has a Classification of Reaction to Fire Performance in accordance with EN 13501-1:2007 +A1:2009 of ‘A1’.

Deployment

Full.

Activation

Commences movement upon initiation of alarm or power or system failure.

Accessories

None.

Visual alert system.

Guidance for specification option:

Light warning system when mains or emergency power is available.

Voice warning.

Guidance for specification option:

Audio or spoken multi message facility when mains or emergency power is available.

Frame colour/ finish

Galvanized steel.

Powder coated.

Guidance for specification option:

Available upon request, insert colour requirements.

Type

Face fixed.

Reveal fixed.

Fixing

Face fixed.

Top fixed.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
IFC
-

1

Revit

Revit 2017

1

Third party certifications

Warrington Fire

Warrington Fire

Horizontal Duplex Certificate

Literature

FireMaster® Concertina™  Active Fire Curtain Barrier

FireMaster® Concertina™ Active Fire Curtain Barrier

Case studies

The Louvre Museum, Abu Dhabi - FireMaster Horizontal and FireMaster Fire Curtains

The Louvre Museum, Abu Dhabi - FireMaster Horizontal and FireMaster Fire Curtains