Verified by manufacturer 4 days ago
Glass louvres
Certificate of constancy of performance
Certificate type
The EN Seefire is an EN 12101-2 certified louvred ventilator for smoke and heat exhaust, day-to-day ventilation, and daylight entry, with multiple variants and installation options.
Suitable for smoke and heat exhaust, day-to-day ventilation, and daylight entry, with multiple variants and installation options.
The EN Seefire is a CE-marked natural louvred ventilator certified to EN 12101-2:2003. It offers both smoke control and day-to-day ventilation, with options for natural daylight via polycarbonate or glass blades. The unit is available in multiple variants, sizes and control options, including pneumatic, electric, or manual operation. Its durable aluminium construction, easy installation, low maintenance and wide application range make it ideal for industrial and commercial buildings.
Product Highlights:
Product Technical Information
Dimensions:
Base:
The base is available in different heights and designs (conical or straight). An insulated version of the base is also available.
Louvres:
The ECO is available with the following louvre variants:
Controls:
The ECO louvred ventilator is either opened or closed manually, electrically, pneumatically or by a combination of electric motor and pneumatic cylinder. Single or double operations can be used.
The following drives are available:
Installation:
Available in many different flange sizes and types which makes it easy to fix it onto curb and into most types of roofs, glazing systems and façade systems.
Certification and Test Results:
In accordance with EN 12101-2:
In accordance with EN 1873:
Thermal Performance (U value):
*Subject to size, configuration and installation type.
Acoustics:
Up to 15.0 dB.
Color | Silver Other |
Material | Aluminium Glass Polycarbonate |
Shape | Rectangle Square |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/47 Roof ventilators L10/490 Roof ventilators H11/140 Louvres |
Product range |
Classification data | |
Standard | To BS EN 12101-2. Guidance for specification option: CE marked. |
Mounting | Onto a curb. Into glazing. Into curtain walling. Into roof sheeting. |
Aerodynamic free area | Manufacturer's standard. Guidance for specification option: Consult manufacturer's literature for details, based on throat length and width. Aerodynamic coefficient (Cv): up to 0.68. |
Reliability classification | Re 1000. Guidance for specification option: 10 000 cycles. |
Snow load classification | Up to SL 2000. |
Low ambient temperature classification | T (-25). Guidance for specification option: T (00) to T (-25). |
Wind load classification | Up to WL 4000. |
Resistance to heat classification | B300. |
Arrangement | Louvred. |
Dimensions | |
Length | 705 mm. 838 mm. 971 mm. 1104 mm. 1237 mm. 1370 mm. 1503 mm.. 1636 mm. 1769 mm. 1902 mm. 2035 mm. 2168 mm. 2301 mm. 2434 mm. 2567 mm. 2700 mm. 2833 mm. 2966 mm. 3099 mm. 3232 mm. 3365 mm. 3498 mm. Manufacturer guidanceThroat length (body length = throat length + 23 mm). Flange widths and lengths are variable and need to be clarified in each instance. For the minimum dimensions of these, add 140 mm to the throat length. |
Width | 576 mm. 726 mm. 876 mm. 1026 mm. 1176 mm. 1326 mm. 1476 mm. 1626 mm. 1926 mm. 2000 mm. 2126 mm. 2326 mm. Manufacturer guidanceThroat width (body width = throat width + 98 mm). Flange widths and lengths are variable and need to be clarified in each instance. For the minimum dimensions of these, add 140 mm to the throat width. |
Controls | Electric, 24 V d.c. Electric, 230 V a.c. Pneumatic. Manual. |
Initiation | Manual. Guidance for specification option: Manual controls only. Double-action locking. Guidance for specification option: Pneumatic or electric controls only. Failsafe open. Guidance for specification option: Pneumatic or electric controls only. Failsafe closed. Guidance for specification option: Pneumatic or electric controls only. |
Materials | |
Ventilator | |
Frame | Corrosion-resistant aluminium alloy grade 3005, insulated. Corrosion-resistant aluminium alloy grade 3005, uninsulated. Manufacturer guidanceIn accordance with EN 573-3, with stainless steel fixings. |
Louvres | Single-skin wired glass. Single-skin laminated glass. Single-skin toughened glass. Manufacturer guidanceThere are some restrictions on the maximum size of the ventilator with glass louvres; consult manufacturer for details. |
Finish | Mill finish. Principal components polyester powder coated. Guidance for specification option: 75 µm thick as standard. |
Colour | Natural. RAL. |
Seals | Rubber seals. |
Guards | Not required. Bird. Burglar. Insect. |
Accessories | Manufacturer guidanceConsult manufacturer for options and insert requirements. |
Resistance to fire | E. Guidance for specification option: To EN 13501-1. |
U-value | Up to 1.52 W/m²K (insulated); up to 1.52 W/m²K (uninsulated). Guidance for specification option: Subject to size, configuration and installation type; consult manufacturer for details. Insulated louvres also available (double-skin aluminium only). |
Sound insulation | Up to 11 dB Rw. |
Material | Aluminium Glass Polycarbonate |