Application

  • For use with fire-rated ceilings.
  • Suitable for multi-home buildings.

Description

Downlight Fire Hoods are designed to reinstate the fire and acoustic performance of ceilings and/or floor constructions when penetrated by downlighters or blank openings if lights are removed for maintenance.

 

The Downlight Fire Hood is made from an intumescent flexible mineral wool material allowing it to be installed through the hole cut into the ceiling membrane. The fire hood also includes small ventilation holes, which allows hotter operating downlighters to ventilate, a small pre-cut hole for the light fitting cable to pass through and a steel clip to hold the hood in place. In the event of a fire the intumescent material will expand to enclose the ceiling cutout, cable and ventholes, providing effective fire resistance, for integrity (E) and insulation (I) for 30, 60 or 120 (EI 30/60/120) depending upon the ceiling and floor joist construction, even if the downlight is removed and replaced.


Features and benefits:

  • A fire-rated product, reinstating ceiling fire protection up to EI 120
  • Tested for minimal acoustic noise transfer.
  • Ventilated design – developed to reduce heat build-up within the firehood enclosure using a ventilated system.
  • Suitable for halogen and LEDs - available in three sizes.
  • Flexible and lightweight - designed to be easily and quickly installed from below ceilings with no special tools required.
  • Compatible with new and retrofit solutions - does not need to be removed when changing light fittings.
  • No maintenance required after installation.

General information

Color

Black

Material

Mineral wool

Shape

Circle

Length

Outside diameter.

150 mm

200 mm

250 mm

Height

150 mm

200 mm

250 mm

Uniclass

Pr_70_70_48_48 Luminaire smoke hoodsPrimary

CAWS

null General purpose luminaires

null Luminaires

P12/150 Loose fire-stopping

Specification data - Luminaire smoke hoods Enhanced data

Standard

To BS EN 1365-2.

Smoke hoods and blankets

Fire resistance: Provides integrity (E) and insulation (I) for 30, 60 or 120 minutes (EI 30/60/120) depending upon the ceiling and floor joist construction. Consult manufacturer's literature and insert requirements.

-

Dimensions

150 x 150 mm.

Cut out size range diameter 50–75 mm.

200 x 200 mm.

Cut out size range diameter 76–100 mm.

250 x 250 mm.

Cut out size range diameter 101–140 mm.

Wattage

35 W (maximum).

LED lamp wattage, in relation to heat output