DEVIsnow™ 20T/ 30T/ 300T Heater Cable - Heating Cable

Verified by manufacturer 18 days ago

DEVIsnow™ 20T

Danfoss Ltd Variant:
Third party certifications:
  • EPD

    EPD

    Certificate type

Self-limiting heating cable, for ice and snow melting applications.

Jump to:
+44 (0) 7842406202 Website

Application

Suitable for melting snow and ice on roofs, in gutters, down drain pipes and on the ground.

Should not be placed in direct contact with bitumen roofs.

Description

360° fully screened, twin conductor self-limiting heating cable with a tough outer sheath.

Features and benefits:

  • Fast and easy to install: the cold lead has solid conductors with a clearly visible connection.
  • Multiple outdoor applications.
  • Safe and robust.
  • Long lifetime: all cables are tested for Ohmic resistance, high voltage and material controls.
  • Provides maximum protection.
  • UV stable.
  • Available with various options for voltage, length, and cold leads.
  • Compliant with IEC 60800.

Note: The cables must be over-temperature protected by a thermostat.

General information

Color

Black

Material

PVC

Copper

Foil

Other

Guidance for specification option:

Fluorinated ethylene propylene (FEP).

Shape

Other

Length

Bespoke

Height

7 mm

Manufacturer guidance

Cable thickness.

Warranty description

20 year

Uniclass

Pr_70_60_36_76 Self-regulating trace heating cablesPrimary

CAWS

T90/478 Underfloor electric heating cables

S90/565 Trace heating tape for pipework

Specification data - Self-regulating trace heating cables

Standards

To IEC 60800.

Arrangement

Multi circuit.

Guidance for specification option:

DEVIreg™ 850 controller.

Single circuit - DIN rail.

Guidance for specification option:

DEVIreg™ 316 controller.

Single circuit - surface mounted.

Guidance for specification option:

DEVIreg™ 610 controller.

Maximum withstand temperature

-

Power on

70°C.

Power off

90°C.

Power output

20 W/m.

Voltage rating

230 V a.c.
400 V.a.c.

Cable construction

-

Conductors

Twin.

Electrically conductive covering

Alu-foil.

Overjacket

PVC.

Colour

Black.

Ingress protection (minimum)

IPX7.

Insulation

Fluorinated ethylene propylene (FEP) insulation.

Cable length

-

Manufacturer guidance

Consult variant datasheets and insert requirement.

Installation temperature

-5°C (minimum).

Deformation capability

1500 N.

Sustainability data

Country of product manufacture

Poland

Material

PVC
Copper
Foil
Other

Guidance for specification option:

Fluorinated ethylene propylene (FEP).

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

0.27 kg CO₂ eq/unit

Guidance for specification option:

2.74E-01.

Manufacturer guidance

See EPD for details.

Third party certifications

Certified

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

EPD

EPD

DEVIsnow EPD

Literature

DEVIsnow 20T data sheet

DEVIsnow 20T data sheet

DEVIsnow 30T data sheet

DEVIsnow 30T data sheet

DEVIsnow 300T data sheet 230-400V

DEVIsnow 300T data sheet 230-400V

Heating cables installer guide

Heating cables installer guide

DEVIconnecto FACT sheet

DEVIconnecto FACT sheet

DEVI ground application

DEVI ground application

DEVI roof applications

DEVI roof applications

Case studies

A Norwegian Homeowner's Solution for a Safe Driveway in Winter

A Norwegian Homeowner's Solution for a Safe Driveway in Winter

Electric heating system to prevent the condensation in the Woolworths Distribution Centre

Electric heating system to prevent the condensation in the Woolworths Distribution Centre

Similar products from Danfoss Ltd

DEVIhotwatt™  45/ 55/ 70 Heater Cable - Heating Cable

DEVIhotwatt™ 45/ 55/ 70 Heater Cable - Heating Cable

DEVIpipeguard™ 10/ 25/ 33 Heater Cable - Heating Cable

DEVIpipeguard™ 10/ 25/ 33 Heater Cable - Heating Cable

DEVIpipeguard™ 10/ 25/ 33 LSZH Heater Cable - Heating Cable

DEVIpipeguard™ 10/ 25/ 33 LSZH Heater Cable - Heating Cable