Verified by manufacturer 1 year ago
A-3105 ventilation louvres with RSV-5700 rain defence louvres to the rear
Double-bank architectural louvres with a continuous blade appearance across a facade, offering a high level of rain defence.
Suitable for applications where a continuous blade appearance is required across a facade and a high level of rain defence needs to be maintained.
Double-bank architectural louvres with a continuous blade appearance across a facade, offering a high level of rain defence.
Features and benefits:
Color | Silver Guidance for specification option: Unfinished (aluminium). Other Guidance for specification option: Any RAL Classic colour available. |
Finish | Powder-coated Mill Anodized |
Material | Aluminium |
Shape | Rectangle |
Length | Manufacturer guidanceDouble bank louvre depth. Varies depending on combination of front/back models selected. |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/54 Louvres H11/140 Louvres L10/650 Metal louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert requirements (height x width) or insert As drawing or As schedule. Typical unit depth (front blades are fitted to back louvre with braces): 208 mm. |
Material | Aluminium. |
Finish | Mill finish front louvre/ matt black rain defence module.Guidance for specification option: Standard. Anodized (clear) front louvre/ matt black rain defence module.Anodized (colour) front louvre/ matt black rain defence module.Guidance for specification option: Insert colour requirements (front louvre). PPC, matt, colour front louvre/ matt black rain defence module.Guidance for specification option: Insert colour requirements (front louvre only). Standard for polyester powder-coated finishes. 30 gloss units. PPC, gloss, colour front louvre/ matt black rain defence module.Guidance for specification option: Insert colour requirements (front louvre only). 70 gloss units. Manufacturer guidanceRain defence is polyester powder-coated (PPC). |
Colour | As Finish. |
Construction | Front louvre blades fitted to rear bank units using blade braces, for continuous blade appearance. |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class A up to 3.5 m/s.Guidance for specification option: Consult manufacturer's literature for further details. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 3: Airflow coefficient Ce (entry): 0.260; Cd (discharge): 0.232. |
Louvre configuration | |
Number of banks | Two. |
Blade orientation | Horizontal (horizontal); vertical (rear rain defence module). |
Blade pitch | 75 mm (front louvre); 51 mm (rear rain defence module). |
Blade angle | 40°. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
|
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. Manufacturer guidanceFor placement behind ventilation louvres in non-active areas, keeping costs down. |
Material | Aluminium |
CS Louvres - Screening Louvres - Visual Screening Louvres
CS Louvres Rain Defence Louvre B-7505 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre PL-5700 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5605 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5900 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSH-5700AL - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSV-5700 - Class A Rain Defence Louvres
CS Louvres Ventilation Louvre A-3105 - Modular Ventilation Louvres
CS Louvres Ventilation Louvre A-3105C - Continuous Line Ventilation Louvres
CS Louvres Ventilation Louvre A-4085 - Modular Ventilation Louvres