Verified by manufacturer 2 months ago
CR2 fire damper
UK Conformity Assessed (UKCA)
Certificate type
DoP
Certificate type
Warringtonfire
Certificate type
Circular EIS fire damper with a fire resistance of 60, 90 or 120 minutes depending on the installation type, both for motorized and non-motorized applications. (previously known as FD and FSD / MFSD)
Circular EIS fire damper with a fire resistance of 60, 90 or 120 minutes depending on the installation type, both for motorized and non-motorized applications.
(previously known as FD and FSD / MFSD)
CR2 certified installations and sealing methods:
CR2 fields of application:
CR2 building applications:
Circular EIS fire damper with a fire resistance of 60, 90 or 120 minutes depending on the installation type, both for motorized and non-motorized applications.
(previously known as FD and FSD / MFSD)
CR2 Distinct Product Features (incl. specifications):
CR2 user benefits:
CR2 range:
CR2 configurations & options:
Notes:
Color | White |
Finish | Galvanized Guidance for specification option: Casing (steel). Epoxy |
Material | Steel Guidance for specification option: Casing. |
Shape | Circle |
Length | 375 mm 500 mm |
Width | 200 mm 250 mm 315 mm 355 mm 400 mm Manufacturer guidanceDiameter. |
Height | 200 mm 250 mm 315 mm 355 mm 400 mm Manufacturer guidanceDiameter. |
Warranty description | One year |
Uniclass | |
CAWS | U90/443 Dampers, fire/ smoke |
Standard | |
Fire dampers | To EN 15650:2010. |
Test | To EN 1366-2.Guidance for specification option: Up to 500 Pa. |
Classification | To EN 13501-3. |
Arrangement | Single-blade. |
Classification | Guidance for specification option: Up to EI90 dependent upon installation requirements; consult manufacturer and insert details. |
Material | Galvanized steel.Guidance for specification option: Tunnel casing. Consult manufacturer for details of other components. |
Accessories | UL inspection opening.Guidance for specification option: Inspection opening to visually determine the state and the position of the damper, by using an endoscope (see INSPECAM digital endescope). None. |
Fusible links | |
Fusing temperature | 72°C. |
Dimensions | 200 mm diameter, 345 mm long. 250 mm diameter, 345 mm long. 315 mm diameter, 345 mm long. 350 mm diameter, 345 mm long. 400 mm diameter, 345 mm long. |
Pressure loss | Guidance for specification option: Insert details, dependent on required damper size and air flow/air speed; consult manufacturer's technical literature for details. |
Air tightness | Class B. Class C. Guidance for specification option: For diameter >315 mm only. Manufacturer guidanceTo EN 1751. |
Thermal release mechanism | Actuator - ONE T 24 V. Actuator - ONE T 230 V. Actuator - ONE-X 24 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - ONE-X 230 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - Belimo 24 V. |
Third-party certification | CE marked BCCA-0749-CPR-BC1-606-0464-15650.02-2517. |
Country of material origin | Europe |
Country of product manufacture | Belgium |
Material | Steel Guidance for specification option: Casing. |
Platform | Compatible | Version |
---|---|---|
- | 1 |
CR120 - Circular EIS Fire Damper (max Ø 315mm) - Fire Damper
CR60 - Circular EIS Fire Damper (max Ø 315mm) - Fire Damper
CR60-1S - "ZERO liabilities" - EIS Circular Fire Damper (max Ø 315mm) - Fire Damper
CU-LT - Rectangular EIS Fire Damper (max W800 x H600 mm) - Fire Damper
CU2 - Rectangular EIS Fire Damper (max W1500 x H1000 mm) - Fire Damper
CU2/B - Large Rectangular EIS Fire Damper - Maximum Four Individual Fire Dampers
CU4 - Rectangular EIS 4Hours Fire Damper - Fire Damper