Verified by manufacturer 3 months ago
CR120 fire damper
DoP
Certificate type
UK Conformity Assessed (UKCA)
Certificate type
Classification report acc. to EN 13501-3
Certificate type
Circular EIS fire damper with a fire resistance of 60, 90 or 120 minutes depending on the installation type, both for motorized and non-motorized applications. (previously known as FD and FSD / MFSD)
Circular EIS fire damper with a fire resistance of 60, 90 or 120 minutes depending on the installation type, both for motorized and non-motorized applications.
(previously known as FD and FSD / MFSD)
CR120 Certified installations and sealing methods
CR120 Fields of application
CR120 Building applications
Circular EIS fire damper with a fire resistance of 60, 90 or 120 minutes depending on the installation type, both for motorized and non-motorized applications.
(previously known as FD and FSD / MFSD)
CR120 Distinct Product Features (incl. specifications)
CR120 User Benefits:
CR120 Range:
Notes:
Color | White Silver |
Finish | Galvanized Guidance for specification option: Casing (steel). Epoxy |
Material | Steel Guidance for specification option: Casing. |
Shape | Circle |
Length | 345 mm Guidance for specification option: Standard models. 500 mm Guidance for specification option: L500 models. |
Width | 100 mm 125 mm 150 mm Guidance for specification option: Not available for CR60-1S models. 160 mm 180 mm Guidance for specification option: Not available for CR60-1S models. Manufacturer guidanceDiameter. |
Height | 100 mm 125 mm 150 mm Guidance for specification option: Not available for CR60-1S models. 160 mm 180 mm Guidance for specification option: Not available for CR60-1S models. Manufacturer guidanceDiameter. |
Warranty description | One year |
Uniclass | |
CAWS | U90/443 Dampers, fire/ smoke |
Standard | |
Fire dampers | To EN 15650:2010. |
Test | To EN 1366-2.Guidance for specification option: Up to 500 Pa. |
Classification | To EN 13501-3. |
Arrangement | Single-blade. |
Classification | Guidance for specification option: Up to EI90 dependent upon installation requirements; consult manufacturer and insert details. |
Material | Galvanized steel.Guidance for specification option: Tunnel casing. Consult manufacturer for details of other components. |
Accessories | Inspection opening in tunnel body.Limit switch (open/closed).Guidance for specification option: To suit specified thermal release mechanism. None.Manufacturer guidanceSee also Thermal release mechanism below. |
Fusible links | |
Fusing temperature | 72°C. |
Dimensions | 100 mm diameter, 345 mm long. 125 mm diameter, 345 mm long. 150 mm diameter, 345 mm long. 160 mm diameter, 345 mm long. 180 mm diameter, 345 mm long. |
Air tightness | Class C. Guidance for specification option: To EN 1751. |
Thermal release mechanism | Actuator - ONE T 24 V. Actuator - ONE T 230 V. Actuator - ONE-X 24 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - ONE-X 230 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - Belimo 24 V. |
Third-party certification | CE marked BCCA-0749-CPR-BC1-606-0464-15650.02-2517. |