Coopers SmokeStop® D600A
Description

An electrically operated SmokeStop® D600A active smoke curtain barrier assembly used to form a virtually continuous barrier against smoke.

SmokeStop® D600A active smoke curtain barrier assemblies comprise a metallic fabric wound on to a steel roller, powered by an internal 24V dc electric motor, enclosed within a 1.2 mm (0.047 in) Stainless Steel box.

A bottom bar is fitted to the bottom edge of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.

The 24V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position.

The SmokeStop® D600A active smoke curtain barrier assemblies have been tested to the requirements of BS EN 12101:2006, Annex B for ‘Reliability and response times’ (1000 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.15m/s). The SmokeStop® D600A active smoke curtain barrier assemblies have been tested to the requirements of BS EN 12101:2006, Annex C for ‘Permeability of materials to smoke’ (0.3m3/h/m2. The SmokeStop® D600A active smoke curtain barrier assemblies have been tested to the requirements of BS EN 12101-1:2006, Annex D for ‘Temperature/Time Resistance Tests’ (120 minutes integrity).

Period of Fire Resistance:

120 minutes (2 hours) integrity

Classification:

D120. D600A, A2-s1, d0, Class “0”

Certification:

Complete barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012.

Complete barrier assemblies are certified with an independent accredited certification body operating an accredited UKAS scheme for installation, commissioning and servicing.

Operation:

SmokeStop® D600A active smoke curtain barrier assemblies commence movement upon initiation of BMS alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.

In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. During this period, the SmokeStop® D600A active smoke curtain barrier assembly will deploy on receipt of a signal. At the end of the period, the Barrier assembly will deploy.

Product certification, performance and/ or testing:

  • Complete SmokeStop® D600A active smoke curtain barrier assemblies are certified by an independent accredited certification body operating to ISO/IEC 17065:2012.
  • Complete SmokeStop® D600A active smoke curtain barrier assemblies are certified with an independent accredited certification body operating an accredited UKAS scheme for installation, commissioning and servicing.
  • Complete SmokeStop® D600A active smoke curtain barrier assemblies have been tested for fire resistance to BS EN 1634-1. The Barrier assembly achieved 120 minutes Integrity.
  • Complete SmokeStop® D600A active smoke curtain barrier assemblies have passed tests to BS EN 12101:2006, Annex B for ‘Reliability and response times’.
  • Complete SmokeStop® DH120 active smoke curtain barrier assemblies have passed tests to BS EN 12101:2006, Annex C for ‘Permeability of materials to smoke’.
  • Motor(s) used within SmokeStop® D600A active smoke curtain barrier assemblies have passed elevated temperature operational tests to BS 8524-1:2013, Annex G.

Approving standards:

The following standards apply to this product:

  • BS EN 12101-1:2006, Smoke and heat control systems: Part 1 – Specifications for smoke barriers
  • BS 476 Pt 6; Fire propagation
  • BS 476 Pt 6; Fire propagation
  • BS EN ISO 1716:2010; Determination of the heat of combustion for building products
  • BS EN 13823:2010; Reaction to fire test for building products
  • BS EN 13823:2010; Reaction to fire test for building products
  • BS 6853:1999: Annex B.2; Determination of weighted summation of toxic fume
  • BS EN 14184-1:2011; Determination of formaldehyde – Part 1: Free and hydrolysed formaldehyde
  • BS 8524-1:2013, Annex G, “Test method for reliability of motor operation at elevated temperatures”
  • BS EN ISO 9001:2015, Quality management system
  • BS EN ISO 14001:2015, Environmental management system

General information

Finish

Galvanized

Powder coated

Available upon request, insert colour requirements.

WarrantyDescription

One year warranty from date of commissioning

Uniclass 2015

Pr_30_59_84_73 Roller shuttersPrimary
Specification data - Roller shutters

Product Reference

Coopers SmokeStop® D600A

Standard

BS EN 12101-1+A1, BS EN 1363-1, BS EN 1634-3, BS EN 13501-4, BS EN ISO 1716, BS EN 13823, BS EN 13501-1, BS 476-6, BS 476-7

Opening sizes

Insert requirements.

Arrangement

Upside down

Vertical

Frame and guides

-

Material

Steel

Finish

Galvanized

Powder coated

Available upon request, insert colour requirements.

Side channels

-

Type

End fixed

Recessed fixed

Recommended 5 mm gap between side guide and building material.

Concealment

Flush fit

Suspended ceiling with recessed shadow gap

Suspended ceiling with patented SLAT™

Self levelling access trim.

Fixing

Face fixed

I beam

Soffit fixed

Unistrut and drop rods

Uniclass 2015 Title

Active smoke barriers

Standard product features

Finish:

All surfaces galvanized steel. Powder coated finish available upon request.

Material:

The curtain material type is EFP™ 2/A2, which is a medium-weight glass fibre fabric. It has an area weight of 455g/m2 -5%, +10%.

The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)

The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products)

The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item)

The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos)

The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method)

The fabric has a classification in accordance with EN 13501-1 as: • A2-s1, d0

Size:

Available in unlimited widths and drops up to 10.5 m. Power supply size (w x h x d): 400 x 500 x 210 mm.

Motor control unit size (w x h x d):

300 x 200 x 80 mm.

Warranty description:

One year.

Country of manufacture:

United Kingdom.

Digital objects
Platform Compatible Version Certified to
Revit

Revit 2017

8

2.0
IFC
-

8

2.0
Download now from NBS National BIM Library