NBS Source
I'm a manufacturer
Compare variants

Conventional Zone Monitor Module

Verified by manufacturer 2 days ago

Conventional IS Zone Monitor - M210EA-CZR

Morley-IAS Variant:

Conventional zone monitor module allows a zone of non-addressable detectors to communicate with a Morley IAS analogue addressable system.

Jump to:
+44 (0) 203 4091779 Website

Application

Conventional zone monitor modules that allow conventional zones to be integrated into intelligent systems for flexibility in system design and retrofit applications.

  • M210E-CZR: Designed specifically for conventional zones in hazardous areas.
  • M210E-CZ: Standard conventional zone monitoring for normal areas.

Description

The M210E-CZ and M210EA-CZ/CZR conventional zone monitor modules provide a means of connecting zones of non-addressable detectors to a Morley-IAS analogue addressable fire alarm system. These modules allow conventional zones to be integrated into intelligent systems for flexibility in system design and retrofit applications.

The M210E-CZR is supplied with a built-in resistor, making it particularly suitable for use in hazardous areas requiring intrinsically safe (IS) equipment. The M210EA-CZ allows the conventional zone to be powered either from the analogue loop or from an external power supply. When powered externally, the zone and supply are fully isolated from the loop to maintain system integrity. Fault conditions, including open circuits, short circuits, or activation of the external fault input, are transmitted directly to the control panel.

Features and benefits:

  • Connects conventional detectors and devices to a Morley-IAS analogue addressable system.
  • Conventional zones can be powered from the loop or from an external power supply.
  • Electrical isolation between the communication line, zone wiring, and external power supply when used in external power mode.
  • Automatic fault reporting to the control panel for open circuit, short circuit, or external fault input conditions.
  • Built-in resistor in the M210E-CZR for use with intrinsically safe (IS) equipment in hazardous areas.
  • Suitable for system extensions and retrofit projects where conventional devices need to be integrated into addressable systems.

General information

Color

White

Finish

Smooth

Material

Plastic

Shape

Square

Length

22 mm

Width

93 mm

Height

99 mm

Uniclass

Pr_75_80_30_41 Interface panelsPrimary

CAWS

S92/420 Alarm devices

W90/120 Fire detection and alarm systems in domestic premises

W90/125 Fire detection and alarm systems in non-domestic premises

SKU Code

M210EA-CZR

Specification data - Interface panels

Classification data

Accessories

M200E-SMB - surface mounting box.

Dimensions

99 x 93 x 22 mm.

Manufacturer guidance

H x W x D.

Weight

0.118 kg.

Current

Max standby current external supply: 120 uA @ 24 V.
Max standby current: 6.3 mA @ 24 V.

Power supply

18–28.5 V.

Manufacturer guidance

External power supply voltage.

Electric resistance

50 Ω.

Manufacturer guidance

Maximum series resistance.

Operating temperature range

-20°C to +60°C.

Humidity

5–95% relative humidity (non-condensing).

Ingress protection

IP44.

Guidance for specification option:

Mounted in M200E-SMB.

Sustainability data

Material

Plastic