NBS Source
I'm a manufacturer
Compare variants

Coltlite Glazed and Insulated Natural Louvred Ventilators

Verified by manufacturer 5 months ago

Coltlite CLN (non-thermally broken)

Colt International Ltd Variant:
Third party certifications:
  • Certificate of constancy of performance

    Certificate type

Natural louvred glazed ventilator, suitable for natural day-to-day ventilation and smoke control.

Jump to:
+44 (0)23 9245 1111 Website

Application

Can provide inlet and extract ventilation as well as the entry of natural daylight for most kinds of industrial and commercial buildings. Suited for installation into the facade.

Typical applications are hospitals, schools, shopping centres, apartments and commercial buildings.

Description

Natural louvred glazed ventilator, suitable for natural day-to-day ventilation and smoke control.

Its form and function makes it particularly suited to naturally ventilated buildings where good aerodynamic and measured free area ventilation is required while achieving high acoustic, thermal and aerodynamic performance. Whilst it is primarily designed as a glazed element of the building envelope, it can also be applied as a high specification fire, smoke and air control damper.


Features and benefits:

  • CE marked.
  • Most variants conform to both EN 12101-2 as smoke ventilators; all models conform to EN 14351-1 as natural ventilators.
  • It can provide inlet and extract ventilation as well as the entry of natural daylight for most kinds of industrial and commercial buildings.
  • Achieves high acoustic, thermal and aerodynamic performance.
  • Suited for installation into the facade.
  • Easy to install.
  • Safe in operation.
  • Durable: manufactured from tough, corrosion resistant aluminium alloy, with stainless steel fixings.
  • Manufactured under the ISO 9000 quality standard.
  • Aesthetic design.

General information

Color

Silver

Other

Finish

Anodized

Powder-coated

Material

Aluminium

Glass

Shape

Rectangle

Square

Length

Bespoke

Width

Bespoke

Height

Bespoke

Uniclass

Pr_70_65_04_56 Natural smoke and heat exhaust ventilatorsPrimary

CAWS

H11/140 Louvres

Product range

Natural louvred ventilators
Architectural Louvre Products

Specification data - Natural smoke and heat exhaust ventilators

Standard

To BS EN 12101-2; EN 14351-1.

Mounting

Wall-mounted.

Reliability classification

Re 1000.

Snow load classification

SL 0.

Low ambient temperature classification

T (-15).

Wind load classification

Up to WL 2000.

Guidance for specification option:

Varies with size and options.

Aerodynamic coefficient: Up to 0.56.

Resistance to heat classification

B300.

Arrangement

Louvred, centre pivots.

Guidance for specification option:

Standard.

Louvred, other.

Guidance for specification option:

On request; consult manufacturer and insert requirements.

Dimensions

-

Width

-

Manufacturer guidance

Insert requirements; overall width: 300–2000 mm.

For throat dimensions, subtract 80 mm.

Height

-

Manufacturer guidance

Insert requirements:

Overall height: 250–3000 mm (per ventilator).


For louvre height (blade pitch), see Pitch below.

Controls

Manual (lever).

Manual (crank handle).

Electric, 24 V d.c. motor.

Guidance for specification option:

Frame mounted and painted motor (hidden behind side frame profile) positioned at top or bottom on either side of frame and with a typical operation time of 32 seconds.

Electric, 230 V a.c. motor.

Guidance for specification option:

Frame mounted and painted motor (hidden behind side frame profile) positioned at top or bottom on either side of frame and with a typical operation time of 32 seconds.

Pneumatic cylinder.

Initiation

Local thermal fuse.

Guidance for specification option:

Opens the unit at a pre-selected temperature (pneumatic cylinder control only).

External release signal.

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Insert requirements.

Materials

-

Ventilator

-

Frame

Corrosion-resistant extruded aluminium alloy, non-thermally broken.

Guidance for specification option:

Depth: 47 mm; face frame width: 40 mm.

With stainless steel fixings.

Louvres

Corrosion-resistant extruded aluminium alloy, non-thermally broken.

Glazing

Insulated glazing, clear float glass.

Insulated glazing, clear toughened glass.

Insulated glazing, clear laminated glass.

Composite infill panels.

Manufacturer guidance

Standard thickness: 28 mm (4 mm glass/ 20 mm gap/ 4 mm glass).

Finish

Anodized.

Guidance for specification option:

20 µm thick standard thickness.

Polyester powder-coated.

Guidance for specification option:

60 µm thick standard thickness.

Colour

Natural.

Guidance for specification option:

Anodized finish only.

RAL, single colour.

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Special colours are available on request.

Accessories

None.

Speed/ force reduction device.

Guidance for specification option:

Reduces the speed and force of closing louvres, to reduce the risk of finger squeezing (some electric versions only; consult manufacturer for details).

Pitch

-

Manufacturer guidance

Insert requirements.

Blade pitch (louvre height): 155–355 mm (150–350 mm).

Air permeability

Class 3.

Guidance for specification option:

1.89 m³/h·m² or 0.37 m³/h·m at 50 Pa.

U-value

Up to 1.8 W/m²K.

Guidance for specification option:

Maximum, to EN 10077-1.

Sound insulation

Up to 41 dB.

Guidance for specification option:

Maximum.

Watertightness

Class 5A.

Guidance for specification option:

To EN 12208; watertight at static pressure of up to and including 200 Pa.

Blade angle

Maximum 90°.

Guidance for specification option:

Depends on the drive selected.

Fixing

To curtain walling.

Guidance for specification option:

Using 20 to 30 mm-thick non-thermally-broken glazing frame adaptor.

To structural opening using through frame fixings.

To structural opening using strap fixings.

Third party certifications

Certificate of constancy of performance

Certificate of constancy of performance

Certificate of constancy of performance - Coltlite

Literature

Coltlite glass louvre window

Coltlite glass louvre window