CFS-B
Description

Bandage for fire stopping around insulated (hot/ cold) non-flammable pipes. Suitable for use with copper, steel and pipes from other metals with heat conductivity lower than that of copper (e.g. cast iron, stainless steel, etc.).

Features/ Benefits:

  • Highly versatile - one product for a variety of insulation materials, pipe materials and pipe diameters.
  • Quick and easy to install - no drilling or additional tools needed.
  • No need to interrupt the pipe insulation material within the wall/ floor penetration.
  • Minimal thickness for easy installation in narrow gaps.
  • Good elasticity for optimum flexibility.
  • Fire resistance rating of up to three hours.
  • ETA-10/0212.

Suitable substrates:

Concrete, masonry and drywall.

General information

Uniclass 2015

Pr_65_52_61_15 Concealed intumescent pipe collarsPrimary

CAWS

P12/44 Pipe collar - insulated wrap

Specification data - Concealed intumescent pipe collars

Product Reference

CFS-B

Standard product features

Thickness:

2 mm.

Roll size (l x w):

10 x 0.125 m.

Fire resistance:

Up to three hours, dependent on substrate and application.

Technical properties:

  • Application temperature: -5 to +50°C.
  • Temperature resistance: -20 to +100°C.
  • Reaction to fire (to BS EN 13501-1): E.
  • LEED VOC: 9.2 g/L.
  • Mould and mildew resistance (to BS EN ISO 846): Class 0.

Third party certifications
  • ETA: 10/0212
Similar products from Hilti (Gt Britain) Ltd