Verified by manufacturer 2 days ago
XCL-LB-CH4-RA (flammable gas - analogue)
Large bore aspirating gas detector which provides reliable detection of gases for occupant protection and process monitoring using Aspirating Detection Pipework Network.
Suitable for a range of application areas, for example:
Large bore aspirating gas detector which provides reliable detection of gases for occupant protection and process monitoring.
This configuration utilizes the aspirating smoke detection (ASD) pipe networks (25 mm/ 27 mm OD) to deliver gas detection via multiple hole (multi-point) sampling. The combined solution also provides protection against fire threats.
The VESDA Sensepoint XCL – Large Bore portfolio has a range of gas sensors that addresses a wide range of applications, and through its Bluetooth interface can be paired with a smart devices for commissioning and maintenance. The smart device application (Sensepoint App) provides quick access to detector diagnostic information and simplifies detector configuration, calibration and bump testing.
Features and benefits:
Color | Black |
Material | Polycarbonate |
Shape | Square |
Length | 59 mm Manufacturer guidanceDepth. |
Width | 113 mm |
Height | 113 mm |
Warranty description | One year Guidance for specification option: 12 months from date of shipment. |
Uniclass | |
CAWS | W90/331 Carbon monoxide alarms |
SKU Code | XCL-LB-CH4-RA |
Classification data | |
Standards | |
Functional safety | To BS EN 50270. |
Detector type | Multi-point. |
Gas | Flammable (CAT). Guidance for specification option: 20–100% LEL. |
Ingress protection (minimum) | IP65. |
Display type | Light-emitting diode display (LED). |
Outputs | 4–20 mA analogue. |
Relay type | 2 no. 5 A/ 24 V d.c. programmable relays. |
Third-party certification | EN/ UL/ IEC 61010-1, CSA-C22.2 No. 61010-1-12, RED, FCC, BT SIG, UL 2075 (CO and CH4), AS 1668.2. |
Power supply | 24 V d.c. |
Weight | 500 g. |
Power consumption | <1.7 W. |
Operating temperature | -20 to +50°C. |
Operating humidity | 0–99% RH, non-condensing. |
AtmosphericPressure | 90–110 kPa. |
Cable | Gauge: 0.5–1 mm². Guidance for specification option: Pluggable rising clamp style. |
Accessories | Not required. XCL-LB-CAP - Flow Cap. XCL-LB-ELB - 60° Elbows. XCL-M20-CG - Cable Glands. XCL-LB-FLT-1 - Filter (CAT, NH3, CO2). XCL-LB-COV-1 - Sensor Cover (CAT, NH3, CO2). |
Material | Polycarbonate |