Certificate of constancy of performance
Certificate type
Certified according to EN 12101-2 and VdS-approved, Apollo ATI is a natural smoke and heat exhaust flap ventilator which is primarily used in industrial, commercial and public buildings.
Natural smoke and heat exhaust flap ventilator which is primarily used in industrial, commercial and public buildings.
Certified to EN 12101-2 and VdS-approved, Apollo ATI is a natural smoke and heat exhaust ventilator for industrial, commercial, and public buildings. Its large-area primary flaps provide maximum smoke and heat ventilation during fire emergencies, while integrated side dampers allow rainproof day-to-day ventilation. Aerodynamic vanes prevent water ingress, and side profiles direct rainwater safely onto the roof.
Product Highlights:
Product Technical Information
Dimensions:
Installation:
Available in many different sizes and base types which makes it easy to fix it onto upstand or into most types of roofs.
Base:
Either a single-skin base or a double-skin base with insulation.
Flaps:
The Apollo ATI ventilator flaps have either insulated aluminium panels or various kinds of polycarbonate multi-wall sheets and are clamped in frames made of extruded aluminium profiles. The sheets are installed in such a way that thermal expansion is allowed for, and so there is no damage from screwing through.
The flaps are set at slightly inclined angles, allowing rainwater to drain off, thus preventing them from getting dirty. The flaps have also been subjected to a wide range of tests, e.g. for impact resistance, resistance to hail, acoustic characteristics, and many others.
The following flap variants are available:
Controls:
The Apollo ATI flap ventilator is opened or closed either electrically or pneumatically by two drive units in each case.
The following flap drives are available:
The drives are designed to exactly match the particular requirements of the project, which results in lower operating and cabling costs.
Side Dampers
The side dampers of the Apollo ATI ventilator are opened or closed either electrically or pneumatically by one drive unit in each case.
The following side damper drives are available:
Performance classes:
In accordance with EN 12101-2
Additional performance classes:
Color | Silver Other |
Finish | Mill |
Material | Steel Aluminium |
Shape | Rectangle Square |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/47 Roof ventilators L10/490 Roof ventilators |
Product range |
Classification data | |
Standard | To BS EN 12101-2. |
Opening type | B. |
Mounting | Roof mounted, onto curb. Roof mounted, onto glazing. Onto curtain walling. Roof mounted, onto roof sheeting. |
Aerodynamic free area | Maximum: 5.7 m². |
Reliability classification | Re 1000. Guidance for specification option: 10 000 cycles. |
Snow load classification | Manufacturer's standard. Guidance for specification option: Up to 5700 N/m² (electric), 1500 N/m² (pneumatic). |
Low ambient temperature classification | T (-15). |
Wind load classification | WL 1500. Guidance for specification option: Aerodynamic coefficient (Cv): Up to 0.68. |
Resistance to heat classification | B300. |
Arrangement | Flap. |
Dimensions | |
Length | Manufacturer guidanceInsert requirements, 1000–3000 mm (1 mm increments). |
Width | Manufacturer guidanceInsert requirements, 1000–1900 mm (1 mm increments). |
Height | Manufacturer's standard. |
Controls | Pneumatic cylinders with integral spring return. Guidance for specification option: Snow load: Up to 1500 N/m². 24 V electric actuators. Guidance for specification option: Snow load: Up to 5700 N/m². Manual. |
Initiation | Manufacturer's standard. |
Materials | |
Ventilator | |
Frame | Corrosion-resistant aluminium alloy grade 3005 in accordance with EN 573-3. Guidance for specification option: With stainless steel fixings. |
Louvres | As arrangement. |
Glazing | 16 mm clear polycarbonate lid. Guidance for specification option: Seven skins, six chambers 16 mm opaque polycarbonate lid. Guidance for specification option: Seven skins, six chambers 16 mm grey (non-light transmitting) polycarbonate lid. Guidance for specification option: Seven skins, six chambers 10 mm clear polycarbonate with 6 mm solid external sheet lid. Guidance for specification option: Single chamber. 10 mm opaque polycarbonate with 6 mm solid external sheet lid. Guidance for specification option: Single chamber. 20 mm double-skin insulated aluminium infill panel lid. 32 mm clear polycarbonate lid. Guidance for specification option: 8–10 chambers, U-value of 1.1–1.3 W/m²K. 32 mm opaque polycarbonate lid. Guidance for specification option: 8–10 chambers, U-value of 1.1–1.3 W/m²K. |
Finish | Mill finish. Polyester powder coated. Guidance for specification option: Standard film thickness: 75 µm. |
Colour | Silver. Guidance for specification option: Standard for mill finish. RAL. Guidance for specification option: Many colour options available; consult manufacturer for details and insert requirements. |
Integral upstands | |
Material | Double-skin aluminium (insulated). Single-skin aluminium. Manufacturer guidanceConsult manufacturer for insulation options. |
Finish | To match frame. Mill finish. Polyester powder coated. Guidance for specification option: Standard film thickness: 75 µm. |
Colour | To match frame. Silver. Guidance for specification option: Standard for mill finish. RAL. Guidance for specification option: Many colour options available; consult manufacturer for details and insert requirements. |
Seals | Manufacturer's standard. Guidance for specification option: Rubber; used to reduce air leakage when closed. |
Fixing | Onto curb. Onto glazing. Onto curtain walling. Onto roof sheeting. |
Locking | Double. Failsafe closed. Failsafe open. |
U-value | Manufacturer's standard. Guidance for specification option: As low as 1.5 W/m²K; consult manufacturer for details. |
Resistance to fire | E. Guidance for specification option: To EN 13501-1. |
Air permeability | Class 3. Guidance for specification option: To EN 12207:2000. |
Sound insulation | 28 dB Rw. |
Material | Steel Aluminium |