NBS Source
I'm a manufacturer
Compare variants

AFD Indigo Calcium Sulphate Range - Raised Access Floor System

Verified by manufacturer 3 months ago

Class 3 BSEN

Access Floors Distribution Variant:

Data Centre Raised Access Floor system with calcium sulphate core and factory bonded finishes. Providing high resistance to fire and humidity with a large variety of finishes options available

Jump to:
BOS
01480 367096 Website

Application

Suitable for:

  • Data centres.
  • Communication rooms.
  • Manufacturing facilities
  • Recording studios.
  • IT suites.
  • Equipment rooms.

Description

The Indigo CS Range features fully accessible raised floor panels manufactured using robust calcium sulphate (gypsum fibre) core.


Available in multiple thickness options, ranging from 30–38 mm. With its high-performance core, this range surpasses conventional wood core alternatives, boasting exceptional load-bearing capacity, unrivalled fire resistance, superior acoustic properties, and remarkable moisture resistance


Manufactured with an ABS edge band trim and the choice of a diverse array of factory-bonded finishes including:

  • Anti-static vinyl.
  • High pressure laminate.
  • Rubber and more.


Features and benefits:

  • Fully accessible floor.
  • High load capability and lightweight.
  • Longer fire resistance and non-combustible.
  • Excellent acoustic performance.
  • High moisture resistance.
  • Manufactured using 94% recycled material.
  • Highly anti-static and conductive.

General information

Color

White

Material

Calcium sulphate

Rubber

Vinyl

High pressure laminate (HPL)

Shape

Square

Length

600 mm

Width

600 mm

Height

30 mm

34 mm

36 mm

38 mm

Warranty description

25 year

Uniclass

Ss_30_20_70_37 Hollow floor systemsPrimary
Ss_30_20_70_70 Raised access floor systems

CAWS

K41/130 Raised access floor

K41/130 Raised access floor

Specification data - Hollow floor systems

System performance

Class 1–6+, to BS EN 12825:2001.

System reference

AFD Indigo Calcium Sulphate Range - Raised Access Floor System.

Standards

To BS EN 13213, BS EN 12825.

Products

AFD CS 30.5 mm.

Subfloor Preparation layer

Prepare the subfloor by ensuring the area is clean, swept and clear.
Prepare the sub floor by applying two layers of PVA sub floor sealer.

Structure

M16 pedestal voids 50–250 mm.

M20 pedestal voids >250 mm.

Pedestal

Adhered to the subfloor using AFD 1-Part Pedestal Adhesive.

Guidance for specification option:

Consider mechanical fixing for voids over 600 mm (two fixings per pedestal).

Floor surface

AFD CS 30.5 mm.

System accessories

None.

Bare base.

Guidance for specification option:

Optional, aluminum foil or galvanized steel. Insert requirements.

Stringer for higher voids >600 mm.

Pedestal cap.

Surface finish

Anti-static vinyl.

High pressure laminate.

Rubber.

Fire classification

To EN 13501-1, A2.

Fire resistance

To EN 13501-2, REI 30.

Load class

To BS EN 13213, class 3.

Deflection

Class A.

Load

Ultimate point load: 8 kN.
Working point load: 4 kN.

Safety

2.

Weight

55 kg/m².

Guidance for specification option:

Nominal.

Manufacturer guidance

System weight.

Sound

Airbourne sound (Dnfw): 50 dB.
Impact sound (Lnfw): 69 dB.

Sustainability data

Contains Red List materials

No

Country of material origin

Germany

Country of product manufacture

Europe

Material

Calcium sulphate

Rubber

Vinyl

High pressure laminate (HPL)

Recyclability

100%

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

94 %

Expected Life

25 year

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

IFC
-

1

Literature

AFD Indigo CS Range - Calcium Sulphate Raised Floor System

AFD Indigo CS Range - Calcium Sulphate Raised Floor System