Verified by manufacturer 1 month ago
Vertical smoke windows for automatic opening smoke ventilation. Tested to EN 12101-2:2003 the Addlite Smoke vent window system meets the requirements of opening and closing to EN 12101-2:2003.
These vertical smoke windows are designed to ventilate smoke from building stairwells, corridors and more. The vertical smoke vent windows can be connected to a fire alarm system and in the event of a fire, the window will automatically open to allow the smoke to be vented out of the building offering a safer escape route. Vertical AOV can be installed in walls, facades and anywhere a standard window could be installed.
All multiple occupancy buildings above three stories must have automated environmental and smoke ventilation capabilities to comply with the strict fire safety rules in part B of Building Regulations 2010.
Smoke ventilation has to be certified and CE marked to EN 12101-2 and will eventually require the UKCA mark. Smoke extract windows open to get rid of smoke. The main purpose of an AOV system (Automatic Opening Vent) is to aid evacuation by helping to clear lobbies, stairwells and corridors in the event of a fire through 'smart' smoke control, allowing a safe route to the nearest means of escape for building occupants.
Smoke windows for automatic opening smoke ventilation installed in vertical walls and facades. These window frames are developed to automatically open to expel smoke in the event of a fire. Tested to EN 12101-2:2003, the Addlite Vertical Smoke vent window system meets the stringent requirements of opening and closing and has been rigorously cycle tested for reliability and operation at 300°. The smoke vent window opens within 60 seconds to provide a safe and smoke free escape route.
AOV windows can be manufactured to meet 1 m2 airflow or a 1.5 m2 airflow depending on building requirements. They are available side hung or bottom hung up to 1200 x 1500 mm in single or double window configurations.
Free air calculations
These should be completed by the specialist actuator supplier to ensure that the airflow requirements meet current building regulations.
Product benefits
Addlite AOV windows provide you with all the safety and security of traditional fire rated products, but with PVC-U’s added inherent benefits of:
Product details
The Addlite AOV window is based on the REHAU TOTAL70 system. The system uses an actuator utilising both the reinforced 105.5 mm T Sash and 72 mm outer frame, with the sealed unit utilizing glazing clips.
Glazing
Glass units must be double glazed using 6 x 6 mm toughened glass made into a 28 mm unit with an aluminium spacer.
Reinforcement
All profiles, irrespective of size, must be reinforced. Manufacturing details must be strictly followed.
Window system
Single AOV (Automatic Opening Vent)
A.O.V. Window hardware
Hinge: Trojan “Patriot” 19 hinges. Three per jamb.
Note. Glass weight to be confirmed to ensure hinge is capable of carrying weight of glass unit.
Actuator: S.E. Controls SECO Single chain 900 stroke.
Performance
The performance of A.O.V windows shall be in accordance with:
Ventilation
Project to be supplied and installed with NO TRICKLE ventilation.
Installation
All components and details in the manual must be used and followed. Any deviation will render the product unfit for purpose. It is therefore the responsibility of the fabricator/installer to ensure by the corresponding manufacturing process that all technical and legal requirements are met and the Addlite AOV window products meet the relevant Building Regulations and CE compliance.
Color | White Grey Black Brown Other |
Finish | Gloss |
Material | PVC-U |
Shape | Square Rectangle Other |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | Five year |
Uniclass | |
CAWS | L10/30 PVC-U windows L10/350 PVC-U windows |
Standard | To BS EN 12101-2. |
Opening type | Bottom Hung.Side-Hung. |
Mounting | Wall-mounted. |
Aerodynamic free area | 1 m2.1.5 m2. |
Arrangement | Glazed side hung casement.Glazed bottom hung casement. |
Dimensions | |
Width | Manufacturer guidanceUp to 1200 mm; insert requirements. |
Height | Manufacturer guidanceUp to 1500 mm; insert requirements. |
Controls | S.E. Controls SECO Single chain 900 stroke actuator. |
Materials | |
Ventilator | |
Frame | PVC-U to BS EN 12608 and certified Class A. |
Glazing | 28 mm insulating glazing unit, comprising 4.0 mm toughened clear external pane, 20 mm 90% Argon-filled cavity with aluminium spacer bar, 4 mm toughened Low E internal pane. |
Colour | White RAL 9016.Foil, colour.Guidance for specification option: Consult manufacturer and insert requirements. |
Sill | 95 mm. 150 mm. 180 mm. |
Hinges | Trojan Patriot 19 hinge. Guidance for specification option: Three per jamb. Note. Glass weight to be confirmed to ensure hinge is capable of carrying weight of glass unit. |
Trickle ventilation | None. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Material | PVC-U |
Recyclability | PVC |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 60 % |
Expected Life | Five year |